Real Time Automation, Inc.
26
1-800-249-1612
BACnet MS/TP Slave Object Configuration
– Binary Objects
Click the
Set Up BACnet Names, Units, and COV
button at the bottom of the BACnet MS/TP Slave
Configuration page to access the Object Configuration page for this device.
When in Auto-Configure Mode, these fields are not configurable. You
MUST
be in Manual Configure
Mode.
Follow these steps to configure binary inputs or outputs in Manual Configure Mode:
1)
Select
Binary Input
or
Binary Output
from the upper left dropdown menu.
2)
Select a
Group
to use.
a)
These
group names are defined on this page under the “Group Name” dropdown menu.
3)
Enter a
Name
to identify this object on the network.
The combination of
Group
and
Name
should be unique for each point in the gateway.