BACNet/IP Client Configuration
Click the
BACnet/IP Client
button to access the configuration page.
1)
Select which
Network Interface
to use for this BACnet/IP connection. If using single port
hardware, the Network Interface will default to Ethernet Port only.
2)
Enter a
Device Label
. This is an internal device alias used during data mapping.
3)
Enter the decimal value of the
UDP Port
that the gateway will communicate on (Default is 47808
(0xBAC0)).
4)
Enter a unique
Instance
identifier for the gateway. This Instance must be unique on the
BACnet/IP network.
5)
Enter a
Name
,
Description
and
Location
for the gateway. These are used to identify the gateway
on the BACnet/IP network.
6)
Delay Between Messages
: Enter the length of time to delay between read and write scan line
requests (ms). A value set to 0 means to go as fast as the network allows.
7)
Response Timeout
: Enter the amount of time the gateway should wait before a timeout is
issued for a read/write request (s).
8)
Dependency Protocol
: If enabled, BACnet/IP communication will stop if communication to the
selected protocol is lost.