RS PRO 124-1054 Instruction Manual Download Page 1

 1 / 2

•  35x77mm size.
•  On-Off control.
•  Relay output for cooling or heating control.
•  Single NTC probe input
•  Range -60 to 150°C
•  Ideal for industrial or commercial applications
•  Probe failure setting, output status can be set to 
   ON, OFF or pulse. 
•  Sensor input offset setting.
•  Selectable heating or cooling control
•  0000 or 000.0 units display.
•  Temperature units °C or °F.
•  Can be used as an alarm unit 
•  CE marked according to European Norms.

 230V AC  +%10 -%20,   50/60Hz  or  24V AC/DC      %10

Max. 3VA

Power connector : 2.5mm² screw-terminal, Signal connector : 1,5mm² screw-terminal conenction.

 EN 61326-1 : 2013 (Performance criterion B is satisfied for EN 61000-4-3) 

EEPROM (Min. 10 years)

Max. 100ohm

 EN 61010-1 : 2010 (Pollution degree 2, overvoltage category II)

 12 bit resolution, 100ms sampling time.

 Max. 2000m

 Do not use the device in locations subject to corrosive and flammable gasses.

Max. humidity 80% for temperatures up to 31°C decreasing linearly to 50% relative humidity at 40°C.

0 ... +50  /   

-25... +70

°C

°C(without icing)

According to EN60529;   Front panel: IP65  Rear panel : IP20

 Scale Range

  Accuracy

EN 60751

 -60.0...150.0 °C    -76.0...302.0°F

 ± 1% (for full scale)   ± 1 Digit

 Supply

HOUSING

 Housing Type

 Dimensions 

 Weight 

 Enclosure Materials

CONTROL

 Control Type

 Control Algorithm

 A/D Converter

 Hysteresis

INPUT

 Height

 Ambient/Storage temperature

 Relative Humidity

Protection Class

Input Type

 NTC Sensor Resistance

77mm

61mm 

5mm

35mm

2

 Connection

Cable

Panel

Rubber

Packing

71,5mm

1

29,5mm

 For 8A   Models : 250V AC, 8A   (for resistive load), NO and  NC  control output.

OUTPUT

  Life Expectancy for Relay

 C1 Output

Holding screw
 0.4-0.5Nm. 

Equipment is protected throughout 
by DOUBLE INSULATION

5

6

SUPPLY:

NOTE:

184-253V AC 
50/60Hz 3VA

Line

Neutral

230V AC
Supply 

Switch

Note: 

Cable size: 1,5mm²

Fuse 

F 100 mA 

250V AC

Fuse should 
be connected

1) Mains supply cords shall meet the requirements of  
    IEC 60227 or IEC 60245. 
2) In accordance with the safety regulations, the power 
    supply switch shall bring the identification of the 
    relevant instrument and it should be easily 
    accessible by the operator.

TECHNICAL SPECIFICATIONS

ENVIRONMENTAL CONDITIONS

ELECTRICAL CHARACTERISTICS

 

Power 

C

onsumption

 

Wiring

 Indicator

 EMC

 Safety Requirements

 Data Retention 

 Line Resistance

   4 digits, 12.5mm, 7 segment red LED

 Single-setpoint and alarm control.

 Adjustable between 0.1 and 20.0°C/F.

 Suitable for flush-panel mounting according to DIN 43 700.

 

H35

x

W77

xD61mm 

 Approx. 215g (After packing)  

 Self extinguishing plastics

While cleaning the device, solvents (thinner, 

gasoline

, acid etc.) or corrosive materials must not be used.

Dimensions

For removing mounting clamps:  

Push the flush-mounting clamp 

in direction 

1

 as shown in the 

figure below.Then,pull
out the clamp in direction 

2

 .

 

Depth

Flush mounting 

clamp

Flush mounting 

clamp

Panel cut-out

 Note:  

1)

 Panel thickness should

be maximum 7mm.

2)

 If there is not 60mm free

space at the back side of
the device,it would be 
difficult to remove it from
the panel. 

1241053 & 1241054

 is intended for installation within control panels. Make sure that the device is used only for 

intended purpose. The shielding must be grounded on the instrument side. During an installation, all of the 
cables that are connected to the device must be free of electrical power. The device must be protected against 
inadmissible humidity, vibrations, severe soiling. Make sure that the operation temperature is not exceeded.

All input and output lines that are not connected to the supply network must be laid out as shielded and twisted cables. 
These cables should not be close to the power cables or components. The installation and electrical connections must 
be carried out by a qualified staff and must be according to the relevant locally applicable regulations.

 For 8A   Models : 30.000.000 Switching for no-load operation; 300.000 switching for 8A   resistive load at 250VAC.

1241053/54-E-01-161006

TM

FOR MORE INFORMATION VISIT THIS SITE

http://www.rs-components.com/index.html

124-1053

124-1054

230V ac 

1

EN

Please read this document carefully before using this product. The guarantee will be invalidated if the device is 
damaged by not following instructions detailed in the manual. The company shall not be responsible for any damage 
or losses however caused, which may be experienced as a result of the installation or use of this product.

Instruction Manual
 RS Pro 35 x 77mm ON/OFF Thermostat, NTC,  Single Output 

 

Stock Number: 

124-1053, 124-1054

SET

°C

SET

°F

C1

SET

°C

SET

°F

C1

1

1241054

DIGITAL
THERMOSTAT

Made In Turkey

230V AC +10% -20%

50/60Hz  5VA

250V AC 8A

RESISTIVE LOAD 

C1

1

2

3

4

5

6

7

8

9

10

11 12

NTC

1

1241054

DIGITAL

THERMOSTA

T

Made In Turkey

230V AC +10% -20%

50/60Hz  5VA

250V AC 8A

RESISTIVE LOAD 

C1

1

2

3

4

5

6

7

8

9

10

11

12

NTC

S/N : XXXXXXXXXX

1

1241053

DIGITAL
THERMOSTAT

Made In Turkey

250V AC 8A

RESISTIVE LOAD 

C1

1

2

3

4

5

6

7

8

9

10

11 12

NTC

24V AC/DC ±10%

50/60Hz  5VA

S/N : XXXXXXXXXX