Electro-Pneumatic Positioner
YT-1000 / 1050 series
Product Manual
Ver. 1.30
61
2)
5-Point position:
By setting 5 points (0 %, 25 %, 50 %, 75 %, and 100 %), the outputs can be set accordingly.
Different from 2-point setting, 5 point setting allows the end user to set 0 %, 25 %, 50 %, 75 %,
100 % to their desired positions. All 5 points should be set when using this position.
3)
Set Off position: (Old PCBs with two position slide switch does not have this position.)
If the slide switch is in this position, calibration setting cannot be adjusted. This position is used to
prevent the set-values from changing when the user mistakenly press the buttons after calibration
has been completed. Only calibration setting is restricted from this position and all other
adjustments can be done.
6.4.2
Buttons
Smart Position Transmitter has 5ea buttons
1)
4mA button:
The button is used when setting 0 % position of full stroke during calibration. Position the valve at
0 %, press and hold the button for 2 seconds and the lamp will flash twice quickly. Release the
button, and then the lamp will flash three times quickly again to confirm that the new setting has
been saved.
2)
8mA button :
The button is used when setting 25 % position of full stroke during calibration. Position the valve
at 25 %, press and hold the button for 2 seconds and the lamp will flash twice quickly. Release the
button, and then the lamp will flash three times quickly again to confirm that the new setting has
been saved.
3)
12mA button:
The button is used when setting 50 % position. Position the valve at 50 %, press and hold the
button for 2 seconds and the lamp will flash twice quickly. Release the button, and then the lamp
will flash three times quickly again to confirm that the new setting has been saved.
4)
16mA button:
The button is used when setting 75 % position of full stroke during calibration. Position the valve
at 75 %, press and hold the button for 2 seconds and the lamp will flash twice quickly. Release the
button, and then the lamp will flash three times quickly again to confirm that the new setting has
been saved.