3
x
Operation
FA ROTEX RoCon mb • 09/2017
11
Displaying the operating data overview
On the "Overview" information level, the RoCon mb controller's
display shows the current operating data for the ROTEX HPSU
monobloc compact.
The display of the operating data is split over several screen
pages. Adjust the rotary button to navigate between the screen
pages.
Tab. 3-5 Explanation of the operating data displayed as an overview
Short des-
ignation
Explanation of the display value
Page
1
Mode Current heat pump mode:
- - -: No heat or cooling request
: Heating
: Cooling
: Hot water generation
: Automatic defrost function active
Ext
Current heat pump energy mode:
LT: EVU function HT/NT active and off-peak.
HT: EVU function HT/NT active and peak.
SGN: EVU function Smart Grid active, normal
operation.
SG1: EVU function Smart Grid active, shut-off: no
heat pump operation, no frost protection function.
SG2: EVU function Smart Grid active, switch-on
recommendation, operation at higher target
temperatures, inexpensive electricity.
SG3: EVU function Smart Grid active, switch-on
command and storage tank charging to 70 °C,
inexpensive electricity
- - -: No external mode active, heat pump operates
in standard mode.
RT
Parameter [Room thermostat] / [Interlink fct]
= Off: - - -
Parameter [Room thermostat] = On:
–
: Heat or cooling request
–
: No heat requirement
Parameter [Interlink fct] = On (priority):
– - - -: Frost protection only
– IL1: Normal target feed temperature
– IL2:
– In heating mode, increased target feed
temperature
– In cooling mode, reduced target feed tem-
perature
Pump Current status of the internal heating circulation
pump
V
Actual flow rate in the heating system
EHS
Current output of the backup heater in kW
Pa
ge 2
TV
Current feed temperature downstream of the plate
heat exchanger (t
V1
)
TVBH Current heating feed temperature, poss. down-
stream of the heating support heat exchanger
(t
V, BH
)
TR
Current temperature of heating return (t
R1
)
Tdhw Current temperature in the hot water storage tank
(t
DHW
)
TA
Current outside temperature (measured by the
heat pump outdoor unit temperature sensor)
Psyst Current water-side pressure in the heating system
Page
3
BPV
Current position of mixing valve 3UVB1
(100% = A, 0% = B)
3UVD Current position of mixing valve 3UV DHW
(100% = B, 0% = A)
TA2
Current outside temperature (measured by the op-
tional outside temperature sensor RKRSCA1)
Tliq2
Current refrigerant temperature (t
L2
)
quiet
Indicates the whisper mode status
Glycol Glycol present: 0 (No) / 1 (Yes)
Fig. 3-5
Displaying the operating data overview
At low return flow temperatures and with glycol in the
system, only "ffff" is displayed as the volumetric flow, no
current value.
Short des-
ignation
Explanation of the display value
On
1205 l/h
3 kW
- - -
- - -
48°C
42°C
1°C
1,9 bar
36°C
44°C
46°C
0%
On
2°C
0%
Mode:
Ext:
RT:
Pump:
V:
EHS:
TV:
TVBH:
TR:
Tdhw:
TA:
Psyst:
BPV:
3UVD:
TA2:
Tliq2:
quiet:
0
Glycol:
Info
Overview
Water Pressure