8
x
Errors, malfunctions and messages
8.4
Control and configuration of DIP switches
Ɣ
De-energise the system.
Ɣ
Check the DIP switch setting on the RoCon BM2C printed
circuit board of the ROTEX HPSU monobloc compact, and
adjust if necessary (see fig. 8-5).
The factory setting must not be changed.
Ɣ
Close the controller housing and restore the voltage supply.
8.5
Emergency operation
Emergency heating operation can be maintained if the electronic
controller settings are incorrect by activating the special "Manual
Operation" function on the controller (see controller operating
instructions).
If the 3-way valves are intact, the ROTEX HPSU monobloc com-
pact switches to
heating mode
. The required inflow temperature
can be adjusted with the rotary switch.
Fig. 8-4
Components in the heat pump outdoor unit (simplified sche-
matic)
a
Plate heat exchanger (condenser)
b
Fan motor
c
Fin heat exchanger (evaporator)
e
Filter
f
Electronic expansion valve
g
Shut-off valve (fluid line)
h
Service valve with maintenance connection (gas pipe)
i
Accumulator
k
Refrigerant compressor
n
4-way switch valve (—> heating,
····
> cooling)
R1T
Feed temperature sensor
R2T
Outlet temperature sensor (refrigerant compressor)
R3T
Fluid line temperature sensor
R4T
Return flow temperature sensor
R5T
Centre fin heat exchanger temperature sensor
S1PH
High-pressure switch
S1NPH
Pressure sensor
A
Outdoor unit water inlet valve
B
Outdoor unit water outlet valve
C
Diaphragm expansion vessel
D
Filter
E
Pressure relief valve
F
Vent valve
G
Flow sensor FLS
H
Circulation pump
J
Flow rate switch
Tab. 8-3 Legend for fig. 8-4
WARNING!
Touching live parts can result in an
electric
shock
and lead to potentially fatal injuries and
burns.
Ɣ
Before beginning work on live parts,
disconnect all of the systems circuits
from the power supply
(switch off external
main switch, disconnect fuse) and secure
against unintentional restart.
Fig. 8-5
DIP switch setting on RoCon BM2C
DIP switch settings are not recognised until a brief inter-
ruption to the power supply.