Errors, malfunctions and messages
FA ROTEX HPSU monobloc compact • 09/2017
57
E9041
U4
Transmission fault Electrical components
Communication between heat pump outdoor unit and heat pump
indoor unit disturbed.
–
Wiring or connections, poor contact.
–
No heat pump outdoor unit connected.
–
Printed circuit board A1P (outdoor unit) defective.
–
Main circuit board in the heat pump outdoor unit defective.
Ɣ
Check, replace.
E9042
U5
Communication between printed circuit board A1P (outdoor unit)
and RoCon BM2C disturbed.
Ɣ
See fault code E200.
E9043
U7
Communication between main circuit board and inverter circuit
board in the heat pump outdoor unit disturbed.
–
Main circuit board in the heat pump outdoor unit defective.
–
Inverter circuit board in the heat pump outdoor unit defective.
–
Wiring, poor contact.
Ɣ
Check, eliminate cause, replace.
E9044
UA
Configuration of printed circuit board A1P (outdoor unit) does not
match the heat pump outdoor unit
Ɣ
Replace printed circuit board A1P.
Ɣ
If necessary, contact a ROTEX service technician.
E9045
AJ
heating time (hot
water)
Software
WW heating > 6 hours
Ɣ
Check the heating element.
Ɣ
Check whether the power supply meets the regulations. Check
for frequency fluctuations.
Ɣ
Check the fuses on the printed circuit boards.
Ɣ
Check WW consumption (poss. too high).
Ɣ
Check the building's WW tap.
Ɣ
Confirm that the software and EEPROM on the hydro printed
circuit board match.
E9046
E6
compressor start-
up
Software
System detects an abnormal electricity wave shape 16 times in
5 min
Ɣ
Check whether the power supply meets the regulations. Check
for frequency fluctuations.
Ɣ
Check the compressor.
Ɣ
Check the compressor's connection and wiring.
Ɣ
Check the operation of the expansion valve (fluid return flow).
Ɣ
Check the refrigerant filling capacity, and check for leaks.
Ɣ
After resetting the power supply, check whether the error occurs
when the compressor is not in operation: check the expansion
valve.
E9047
E8
overvoltage
Software
System detects an overcurrent of > 20 A to the compressor for
> 2.5 seconds 16 times in 5 min
Ɣ
Check the compressor.
Ɣ
Check the compressor's connection and wiring.
Ɣ
Check the operation of the expansion valve (fluid return flow).
Ɣ
Check the refrigerant filling capacity, and check for leaks.
Ɣ
Check the power transistor.
Ɣ
Check the outer inverter conductor plate.
Ɣ
Check whether the current flow LED flashes at regular intervals.
Ɣ
Check whether the correct replacement part has been installed.
Ɣ
Check whether the outer main conductor plate is receiving a
power supply.
Ɣ
Check whether the power supply meets the regulations. Check
for frequency fluctuations.
Code
Malfunction /
error message
Component/
Designation
Causes and possible fault elimination
Display Internal