Errors, malfunctions and messages
E9011
C0
Fault flow sensor
Flow sensor FLS or flow
switch (outdoor unit)
Flow sensor FLS or flow switch defective.
Ɣ
Replace flow sensor FLS.
Ɣ
Replace flow switch.
E9012
C4
Fault feed flow
sensor
Feed temperature sen-
sor t
V1
(outdoor unit) or
t
V, BH
Measured value outside of the permissible value range. Sensor or
connecting cable defective.
Ɣ
Check, replace.
E9013
E1
OU main board def
Heat pump outdoor unit
main circuit board
–
Main circuit board in the heat pump outdoor unit defective.
–
Fan motor defective.
Ɣ
Check, replace.
E9014
E3
Coolant over-pres-
sure
High-pressure switch
S1PH in the refrigerant
system (outdoor unit)
Pressure in refrigerant system is too high.
–
High-pressure switch S1PH or fan motor defective.
Ɣ
Check, replace.
–
Poor wiring contact.
–
Flow rate in the heating system too low.
–
Filled refrigerant quantity too high.
Ɣ
Check, replace.
–
Service valves in the heat pump outdoor unit not open.
Ɣ
Open service valves.
E9015
E4
Coolant under-
pressure
Pressure sensor S1NPH
in the heat pump outdoor
unit
Pressure in refrigerant system too low.
–
Refrigerant quantity too low.
Ɣ
Check, eliminate cause, top up refrigerant.
–
Pressure sensor S1NPH in the heat pump outdoor unit defective.
–
Temperature sensor of fin heat exchanger R4T in the heat pump
outdoor unit defective.
–
Solenoid valve in the heat pump outdoor unit not opening.
–
Main circuit board in the heat pump outdoor unit defective.
Ɣ
Check, replace.
E9016
E5
Load protec comp
Electronic overload pro-
tection in the refrigerant
compressor (outdoor
unit)
Refrigerant compressor overload protection has triggered. Pressure
difference in the refrigerant circuit between high and low pressure
side too high (> 26 bar).
–
Refrigerant compressor defective.
–
Inverter circuit board in the heat pump outdoor unit defective.
–
Refrigerant compressor / inverter circuit board wiring, poor con-
tact.
–
Filled refrigerant quantity too high.
Ɣ
Check, replace.
–
Service valves in the heat pump outdoor unit not open.
Ɣ
Open service valves.
E9017
E7
Fan blocked
Fan motor in the heat
pump outdoor unit
–
A fan in the heat pump outdoor unit is blocked.
Ɣ
Check fan for presence of dirt or blockages; if necessary,
clean and free up.
–
Fan motor defective.
–
Fan motor wiring, poor contact.
–
Overvoltage at fan motor.
–
Fuse in the heat pump outdoor unit defective.
–
Inverter circuit board in the heat pump outdoor unit defective.
Ɣ
Check, replace.
E9018
E9
Expansion valve
Electronic expansion
valve (outdoor unit)
–
The electronic expansion valve in the heat pump outdoor unit is
defective.
Ɣ
Check, replace.
E9019
EC
Hot water temper-
ature > 85 °C
Storage tank tempera-
ture sensor t
DHW
The storage tank temperature sensor t
DHW
delivers a temperature
value > 85 °C.
–
Sensor or connecting cable defective.
Ɣ
Check, replace.
E9020
F3
Evaporator over-
temp
Outlet temperature sen-
sor (hot gas sensor) R2T
on the heat pump out-
door unit refrigerant
compressor too high
–
Outlet temperature sensor R2T on the refrigerant compressor
or connecting cable defective.
–
Refrigerant compressor defective.
Ɣ
Check, replace.