32
BA ROTEX HPSU compact 4 - 09/2013
6
x
Parameter settings
6.2.4 Level "DHW Configuration"
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Circl-Pump DHW
Setting for activating a circulation pump.
Off: The optional circulation pump operates synchronously with the switching timer program
activated for generation of hot water.
On: Optional circulation pump operates according to the timer programme [Circulation Time].
E
E
Off
On
Off
-
Circl-Pump Interval
Setting the interval control for an optional circulation pump.
Off: Deactivated
The circulation pump operates continuously throughout the enabled time of the assigned
switching timer program (parameter [Circl-Pump DHW]).
Otherwise: The circulation pump runs cyclically
(Duty ratio: Pump running time = Set value every 15 min).
E
E
Off,
1 - 15 min
Off
1 min
Anti-Legionella day
Setting the day for the thermal disinfection of the circulating tank.
Off: No thermal disinfection
Monday - Sunday: Day for thermal disinfection
Mon - Sun: Daily thermal disinfection
E
E
Off,
Monday
...
Sunday,
Mon - Sun
Off
-
Tab. 6-4
Parameter in rotary switch setting "Configuration", level "DHW Configuration"
6.3 Rotary switch setting: DHW Install
Parameter
Designation
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
1x Hot Water
Start of the one-off heating up of the hot water and the set value [T-DHW Setpoint 1], independ-
ent of the heating programmes.
E
E
0 - 1
0
1
Hyst HP
Switching threshold hot water charging
Stipulates from which heat pump temperature spread the heat pump should be switched on for
hot water charging.
E
E
2 - 20°C
5 °C
1 K
Timer BOH
Delay time after which the reserve heating may support the heat pump in hot water charging.
E
E
20 - 95 min
50 min
1 min
Tab. 6-5
Parameter in rotary switch setting "DHW Install"
6.4 Rotary switch setting: Operating Mode
Parameter
Designation
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Standby
In this operating mode, all internal functions are turned off. Frost protection remains active and
a blocking protection for the pump is guaranteed.
All controllers integrated in the RoCon-system via the CAN bus are also switched at a higher
level to the operating mode when this setting is selected.
Outputs are not free of voltage always.
E
E
-
Reducing
The internal heating circuit provides continuous (24 h per day) regulation to the parameterised
setback temperature. The hot water generation takes place according to [DHW Program 1].
E
E
-
heating
The internal heating circuit provides continuous (24 h per day) regulation to the parameterised
day set room temperature (heating). The hot water generation takes place according to
[DHW Program 1].
E
E
-
Cooling
The internal heating circuit provides continuous (24 h per day) regulation to the parameterised
day room temperature set (cooling). The hot water generation takes place according to
[DHW Program 1].
Frost protection remains active and a blocking protection for the pump is guaranteed.
E
E
-
Summer
The internal heating circuit is turned off. Frost protection remains active and a blocking
protection for the pump is guaranteed. The hot water generation takes place according to
[DHW Program 1].
All controllers integrated in the RoCon-system via the CAN bus are also switched at a higher
level to the operating mode when this setting is selected.
E
E
-
Automatic 1
The internal heating circuit regulates according to the second parameterised timer programme
[HC Program 1] with the individual day room temperatures set. The hot water generation takes
place according to [DHW Program 1].
E
E
-
Automatic 2
The internal heating circuit regulates according to the second parameterised timer programme
[HC Program 2] with the individual day room temperatures set. The hot water generation takes
place according to [DHW Program 2].
E
E
-
Tab. 6-6
Parameter in rotary switch setting "Operating Mode"