[ 50 ]
Warning:
Leaks can lead to gas
escaping, resulting in a risk of
fire and explosions. Never
remove both locking plates on the burner
flange (sealing paint).
4. Checking the flue gas paths
Check all flue gas system components for
damage and soundness; repair, if required.
5. Cleaning the combustion chamber and
burner
Generally, the burner will operate without
creating wear or residues. If contamination or
unsatisfactory combustion values are
discovered, carry out cleaning and adjusting
steps, as required.
Caution: Danger of burning
Burner and boiler parts may
be hot. Let the equipment cool
down sufficiently before touching these
components or wear protective gloves.
Caution: Risk of electric shock
Only work on the burner after
switching the mains isolator
OFF or after interrupting the power supply
and after the boiler body has cooled down
sufficiently.
Only work on the burner after switching the
mains isolator OFF or after interrupting the
power supply and after the boiler body has
cooled down sufficiently.
Fig. 6.1.3: Prior to burner removal
Pull off the ventilation air hose
Step 1: Undo the drain plug
Step 2: Visual control of the connection
and level
Step 3: Visual check of the drain hose
(embrittlement, slope)
Step 4: Check the unrestricted draining
Fig. 6.1.2: Check the condensate drains off OK
Fig. 6.1.4: Turn the pulled off ventilation
air hose to the side
Fig. 6.1.5: Opening the combustion chamber
1 -
Remove the CVBC lid; pull off the connection plug
2 -
Undo the flange nuts
3 -
Pull the burner up
4 -
Remove the burner