[ 37 ]
GSU 25/ GCU 25
GSU 35/ GCU 35
Gas type
Settings for
Output
CO
2
content
O
2
content
Output sett-
CO
2
O
2
content
Test setting
1)
Load
in %
ing
1)
in %
speed
Load
in %
in %
measurement
1)
speed in % in kW
(+/- 0.2 %)
(+/- 0.1 %)
in %
in kW
(+/- 0.2 %)
(+/- 0.1 %)
FULL LOAD
100
25.5
9.4
4.2
100
36.1
9.8
3.5
80
20.2
9.3
4.3
80
28.6
9.6
3.8
STANDARD LOAD
33
7.9
9.2
4.5
33
11.1
9.3
4.4
24
5.5
9.2
4.5
26
8.5
9.2
4.5
FULL LOAD
100
25.5
9.3
4.0
100
36.1
9.6
3.5
80
20.2
9.2
4.1
80
28.6
9.4
3.9
STANDARD LOAD
33
7.9
9.1
4.4
33
11.1
8.9
4.8
24
5.5
9.1
4.4
26
8.5
8.8
4.9
FULL LOAD
100
25.5
11.3
3.8
100
36.1
11.5
3.5
80
20.2
11.1
4.1
80
28.6
11.2
3.9
STANDARD LOAD
33
7.9
10.6
4.9
33
11.1
10.6
4.9
24
5.5
10.5
5.0
26
8.5
10.5
5.0
FULL LOAD
100
25.5
11.5
3.8
100
36.1
11.7
3.5
80
20.2
11.3
4.1
80
28.6
11.4
3.9
STANDARD LOAD
33
7.9
10.8
4.9
33
11.1
10.8
4.9
24
5.5
10.7
5.0
26
8.5
10.7
5.0
1)
Observe warning information! The details in the plain fields correspond to the ROTEX factory settings
Table 5.1.2: Set flue gas values for different gas types
Fig. 5.1.8: Set flue gas values for burner adjustment for GSU 35/GCU 35
2)
Fig. 5.1.7: Set flue gas values for burner adjustment for GSU 25/GCU 25
2)
The data items filled in white represent the ROTEX factory settings
Natural
gas E, H
Natural
gas LL,L
Propane
Butane
Summary of Contents for GasCompactUnit Series
Page 17: ... 17 Fig 3 4 3 Flue gas system sets ...