SuperGuard and Piguard Plus
|
1.09
11.5 Test
The test option is used mostly in the installation process and it enables the installer to check systems.
To test a menu:
1. Press “
SELECT
” and “down” arrow keys simultaneously and hold them together for about two
seconds. The display alternates between the name of the I/O and an ON/OFF sign.
2. Press the arrow keys to allow switching between On and Off.
•
rL.1-7: Relays 1 to 7
•
SPd: Variable speed (check minimum to full
capacity using the arrow keys)
•
AO1-4: Analog outputs 1 to 4
•
t1, t2: Temperature sensors with the A/D
counts blinking on the screen
•
Hu: Humidity sensor A/D counts
•
Ai1-2: Analog inputs 1 to 2
•
Prs: Pressure A/D counts
•
DG1-3: Digital inputs 1 to 3
11.6 Technical Specifications
Power Supply
Mains voltage
Single phase, 115/230 VAC
Main fuse
315 mA
Secondary fuse
1 A
Maximum power consumption
22 VA
Available power for peripheral equipment
Analog Inputs
3 analog inputs for temperature sensors
RTS-2 (Thermistor)
4 analog outputs
20 mA, 0-:-10V
1 humidity sensor input
0-:-3V
2 analog inputs
0-:-5V
Digital Inputs
3 digital inputs
Dry contact, 5 V/2 mAmp
Relays Outputs
8 Normally open power relay
2 HP, 12 Amps, 250 VAC
Variable Speed Output
2.2 KW 10 Amps, 230 VAC; 2.8 HP
1.1 KW 10 Amps, 115 VAC; 1.4 HP
Housing
Dimensions (L x W x H)
92.5 x 73 x 36
Ambient Climate
Operating temperature range
32º to 122º F (0º to 50º C)
Storage temperature range
14º to 158º F (-10º to 70º C)
Indoor Applications
The equipment is designed for use in indoor applications only!