SuperGuard and Piguard Plus
|
1.09
52
11 PIGUARD PLUS
The following sections detail the Piguard Plus functions.
11.1 Cold Start
To execute a cold start, disconnect the power, reconnect the power while pressing the three Piguard
Plus buttons together and hold them for about three seconds. The following appears:
C L d
When this screen appears, the controller preformed a cold start.
CAUTION
Cold Start erases all data and history from the memory and load factory
defaults!
11.2 Set Unit Number
•
Press the two arrow key simultaneously until NO blinks.
•
Set the unit number with the up and down arrows.
•
Press
SELECT
.
11.3 Main Menu
Once the
Piguard Plus
is activated
the main screen appears displaying the inside average temperature
of the rooms. Press
SELECT
for two seconds to allow the user to access the main screen’s information.
•
trg:
The target temperature for the room. (Can be
changed from the Piguard Plus itself only if a
curve was not defined.)
•
rH:
Humidity in room.
•
rH.t
: Target humidity.
•
day:
Growth day for the room.
The display alternates between the name and the figure.
11.4 Calibration
Temperature sensors are very accurate and most likely do not require calibration. However, if calibration is
required, do the following:
11.4.1
Temperature Sensor Calibration
•
Use an accurate thermometer as a reference.
•
Place the thermometer near the temperature sensor.
•
Make sure that the inside temperature is stable.
•
Calibrate the temperature sensor immediately after reading.
11.4.2
Calibration Procedure
1. Press
SELECT
and the “up” arrow keys simultaneously and hold them together for about two
seconds. The display alternates between the sensor number and the temperature measured.
2. Use the arrow key to change the temperature.
3. Press
SELECT
to move through the sensors and the arrows to change temperatures.
NOTE:
Calibration of humidity sensor is done exactly the same way; the only difference is that instead
of measuring temperature, the humidity is measured by an external humidity sensor.