1
2
3
4
1
2
3
4
ON
W - V - U - Motor Wires
The motor has 3 wires.
The common (check label on the motor) usually the yellow one
must be connected to the U output.
The outputs V and W determine the motor rotation direction
(right - left).
Note that the 1st central control must open the gate. If
the 1st control closes the gate, reverse the V and W
wires.
Note that this 1st control is a factory test pattern, if this control
has already been turned on, it will be stored the last activated
end of stroke (open or closed). To do this test, leave the gate
open halfway and start.
N/F - Input 90-240V ~ ac
Automatic source
Voltage input already intercepted
by a 10A bipolar circuit breaker
and grounding the equipment.
CAP- Starting Capacitor
Capacitor according to the motor
power, the wires have no
polarity.
Output GND - 12V
Power supply output for ROSSI
accessory plates, garage light
plate, driver board, door lock
plate, SIA 30 Photocell.
FCH Output - Lock
for interconnecting locking
accessory plate, it is mandatory
to enable
Dip 2
Sensor Hall End of Stroke
The sensor hall identifies the magnets polarity, north
and south. Before attaching the magnets, identify the
FA and FF by moving the magnet on the rack until it
passes in front of the sensor hall that will light the
green led "FA" or red "FF". (If the two magnets light
the same led choose one of the magnets to reverse
the polarity.)
HALL calibration
: If one of the LEDs FA
or FF is lit, with the gate in the middle of the path, the
Hall must be calibrated (remove the energy from the
plate press the LEARN button and with your finger
pressed turn the power on again then release the
button).
SIN -GND - Traffic
light
consists of interconnecting a
signal with the central gate
using the terminals SIN and
GND.
SIN -GND - Garage light.
to
interconnect the garage
LIGHT accessory board.
GND/ANT
LED
ST
LEARN
LED ST - LEARN / MEMORY
:
Delete individual buttons:
This feature allows you to erase from the
central memory the encoding,
independently of the key code, without
affecting others. For this the access key
must be in hand to perform this procedure.
Hold down learn while pressing one of the
key switch you want to delete.
Note:
The
time must be shorter than to delete the
memory.
BOT/GND
•
1 - Soft stop
Enabled
1 - Smoth Stop
Disabled
2
–
Lock
3
–
Pause
4 - Building
•
To enable, set the switch to
ON
position
TX-
NF CM
GND 12V
SIA 30 FS.
- connect the
photocell's GND to
the TX-terminal of
the
control unit
Decrease gate speed shortly before reaching the end of stroke, with two levels of intensity, light or
heavy gate.
TX- 12v
GND 12v CM NF
to enable put DIP 1 to ON and press the SET button (6 times
- lightweight gate) or (7 times to return to the normal level).
Note: Enabling DIP 1 is at normal intensity.
-
Photocell must be switched on in Normally Closed (
NF
)
Wiring diagram WITHOUT FS function
•
2 - Lock
The programming lock when enabled causes the control panel, after receiving an opening control, first
send a pulse to open the lock and after a few seconds starts opening the gate.
•
3- Automatic closing (Pause);
Set the pause switch to ON position and give the opening command. When the open limit switch (FA)
is reached, the ST LED will start flashing in 1-second intervals, allow the desired time to elapse for the
pause value and give the command again. Each flashing indicates 1 second elapsed until 12h (E.g. if
the LED blinks 20 times, the pause time will be 20 seconds. After this operation is completed, the
pause will be programmed, every opening that occurs and elapses in the programmed time will
automatically close the gate.)
To disable this feature, simply put the pause switch in the OFF position. In the next control the pause
will be disabled. (for this type of configuration, it is of utmost importance, for the safety of the user, to
use barrier sensors 'SIA 30'.)
•
4 - Building
NA CM
GND 12V
Note:
Connection mode
compatible with the
previous switches or with
the function Fail Safe
DISABLED (central FS
connection with the jumper
closed).
GND12v
GND12v CM NA
Building - All controls open the gate, that only closes by automatic closing, which will only stop at the
open limit, if there is another control during the opening, central will ignore it. After the gate reaches
the open limit switch it will start the automatic closing time count, the gate will only close after the
scheduled time elapses. If there is a remote control or button control, the time will be reset and the
count will start again. If the gate is closing, any control will make the gate stop and open again. (Note:
In building mode the automatic closing is enabled automatically, just adjust the time in the 1st control.)
Residential - Accepts all controls and pushbutton (1st - control opens, 2nd - to, 3rd – closes
10 - Clutch Adjustment
Clutch Adjustment
•
Adjust trimpot to minimum;
•
Start the engine through the remote control;
•
Gradually increase the drive force until you
move the gate;
•
adjust the trimpot slightly above that
necessary to move the gate.
Note: For compatibility with previous versions, close the Jumper
(Input NA)
-
The gate barrier sensor must be installed with the Transmitter and Receiver.
-
Must be at the same height and in the same alignment, ideal height for installation in gates is 50cm.
- Installation should be done as close as possible to the gate.
-
The certification is valid only with the use of approved ROSSI photocells: SIA 30 FS
11 - Electronic Brake Adjustment
ADJUSTMENT - Adjustment of BRAKE levels
The control unit has 5 levels of electronic brake.
Press and release the SET button at intervals of less than 1sec. according
to the desired level.
Level 1 =
25% of brake - Press 1 time
Level 2 =
50% of brake - Press 2 times
Level 3 =
75% of brake - Press 3 times
Level 4 =
100% brake - Press 4 times
Level 5 =
Press 5 times
NOTE:
At the end of each setting, wait 2 seconds and the ST LED will
blink at which level it is programmed.
Page 6
05 - External button and traffic light / Light 06 - Antenna 07 - Record digital access key
08 - Dip programming
09 - Photocell connection - FAIL SAFE
C
oax
ial
c
abl
e
up t
o 3M
16c
m
• The Switch consists of installing a wrist button
(bell type) on the borne (BOT) of control panel or
interconnect a Receiver.
“The Switch is used for manual driving in cabinets,
driving by interphone or eventual need for driving
from distance by an external button.”
Frequency reception antenna, connect the stripped part of
the 16cm wire on borner - ANT
• If you need a wider range, connect a 2m coaxial cable
on the antenna input:
-On the upper part of the cable you should uncover the
core at 16cm
On the part of connection to the control panel you should
put the core on borne ANT and the mesh at GND like the
drawing at the control panel.
Recording of access key:
• Press and release the learn button on
the control panel;
• With the led on, press one of the buttons
of the key at the end of the recording; it
will flash indicating the programming was
accepted
Repeat the process to record other
buttons.
Note: Time should be shorter than for
deleting the memory.
Deleting the Memory: Press the button
LEARN and keep it pressed until ST LED
goes off; with this procedure, you delete
recorded codes.
Core
Mesh
16cm from core
without mesh
Photocell FAIL SAFE
function.