SURFACE SEARCH
The
Surface Search
command triggers a search for the product surface and
can be used, for example, if the measured level is locked onto a disturbing
object in the tank (see “Configuration Report” on page 7-18).
USING THE SIMULATION
MODE
This function can be used to simulate measurements and alarms.
RRM: choose menu option
Tools > Simulation Mode
:
Figure 7-18. The Simulation
Mode window in RRM.
AMS Suite:
Tools > Service > Simulation Mode
.
HART Command: [1, 2, 2].
WRITE PROTECTING A
TRANSMITTER
A Rosemount 5400 Series transmitter can be password protected from
unintentional configuration changes. The default password is
12345
and it is
recommended that this password not be changed to facilitate service and
maintenance of the transmitter.
RRM:
Tools > Lock / Unlock Configuration Area
.
AMS Suite:
Tools > Service > Lock / Unlock Device
.
HART Command [1, 2, 7].
Summary of Contents for 5401
Page 2: ......
Page 4: ......
Page 10: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series TOC 6 ...
Page 24: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series 2 10 ...
Page 80: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series 5 26 ...
Page 90: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series 6 10 ...
Page 160: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series B 16 ...
Page 174: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series C 14 ...
Page 177: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Index 3 Rosemount 5400 Series ...
Page 178: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series Index 4 ...
Page 179: ......