Rosemount 5300 Series with HART® to Modbus® Converter
May 2016
Reference Manual
00809-0100-4530, Rev DD
399
Rosemount 5300 Series with HART® to Modbus® Converter
Table J-14. Output Variables for Floating Point Format Code 0
Register Name
Register
Number
Note
Slave 1 Status
2000
Bit information in bitfield:
Bit 0: Invalid Measurement Slave 1 PV.
Bit 1: Invalid Measurement Slave 1 SV.
Bit 2: Invalid Measurement Slave 1 TV.
Bit 3: Invalid Measurement Slave 1 FV.
Bit 14: HART bus busy (slave in burst or other master
present)
Bit 15: HTM Task not running (option not available).
Note:
Bit 1-3 is set when Invalid Measurement of Slave 1
Non PV, i.e. all three bits are set simultaneously.
Slave 1 PV
2002
Primary variable from slave 1 represented in IEEE 754
format, using Floating Point Format Code 0.
Slave 1 SV
2004
Secondary variable from slave 1 represented in IEEE 754
format, using Floating Point Format Code 0.
Slave 1 TV
2006
Tertiary variable from slave 1 represented in IEEE 754
format, using Floating Point Format Code 0.
Slave 1 FV (QV)
2008
Fourth variable from slave 1 represented in IEEE 754
format, using Floating Point Format Code 0.