Figure 7-27. Product Level Lowered beneath the Near Zone
Table 7-2. Near Zone Definitions Depending on Software Releases and Probe Type
9.
Verify that the transmitter measures correct product level, otherwise see
and distance calibration” on page 164
.
Rosemount 5300 GWR Series near zone
Firmware version
Rigid probes
Flexible probes
Firmware version earlier than 1.A4
15 in. (0.37 m)
Firmware version 1.A4 or later
40 in. (1 m)
Near Zone