163
Reference Manual
00809-0100-4530, Rev DD
May 2016
Choose the
Interface Level with Submerged Probe
option.
Measurement mode
Interface Level with Submerged Probe
can also be activated in the RRM
software:
1.
In the RRM workspace, select the
Tank
icon.
2.
Select the
Environment
tab.
3.
Select the Measurement Mode
Interface Level with Submerged Probe
option.
4.
Select the
Store
button.
Note
Do not use Measurement Mode
Interface Level with Submerged Probe
in applications when
both Interface Level and Product Level are available.
Figure 7-12. Interface Level Measurements in a Full Chamber
Note
Adjust Surface Threshold if the interface level pulse is not detected. Note that in submerged
mode the interface is picked up by the surface threshold. See also
.
7.8
Analog output calibration
This function lets you calibrate the analog output by comparing the actual output current
with the nominal 4 mA and 20 mA currents. Calibration is done at the factory and normally
the transmitter does not need to be recalibrated.
The analog output calibration function is available via the HART command [2, 8, 1].
In RRM, this function is available via
Setup
>
Output
.
Interface distance
Interface level
Product level is ignored
Interface level is measured