14.
To configure volume calculation, select the
TRANSDUCER1300
block and then the
Volume
tab.
15.
Choose a pre-defined calculation method based on a tank shape that corresponds
to the actual tank. Choose
None
if volume calculation is not desired.
Use Volume offset if you do not want zero volume and zero level to match (for
example if you want to include the product volume below the zero level).
The Strapping Table option is used if the actual tank does not match any of the
available options for pre-defined tanks or if a higher calculation accuracy is desired.
Calculation method:
F
OUNDATION
Fieldbus parameter:
TRANSDUCER 1300 > VOL_VOLUME_CALC_METHOD
Diameter:
F
OUNDATION
Fieldbus parameter:
TRANSDUCER 1300 > VOL_IDEAL_DIAMETER
Tank length:
F
OUNDATION
Fieldbus parameter:
TRANSDUCER 1300 > VOL_IDEAL_LENGTH
Volume offset:
F
OUNDATION
Fieldbus parameter:
TRANSDUCER 1300 > VOL_VOLUME_OFFSET
See
“Volume configuration” on page 91
for more information.