Reference Manual
00809-0100-4799, Rev BA
September 2002
Model 3244MV
3-3
CONFIGURATION
Physical Block
1.
Place the physical block into “Out of Service (O/S)” mode.
2.
Select the “Display” mode, located under the “Device”
pull-down menu.
3.
Turn on the valves to be displayed. Set the desired decimal place.
4.
Download the device.
5.
Select the “Load into PG/PG” option (UPLOAD), located under the
“Device” pull-down menu.
6.
Place the Physical Block into Auto mode.
Transducer Block
1.
Select the “Master Reset” option, located under the “Device”
pull-down menu.
2.
Input the following as desired
•
1
to select restart with defaults
•
4
to restart processor
3.
Click “download” to download the device.
4.
Once the device has restarted, click close.
5.
Select “Change Sensor Type,” method located under the “Device”
pull-down menu. When this method begins, select the desired sensor
type and the connection.
6.
Perform step five for all sensors.
7.
Select the “Load into PG/PG” option (UPLOAD), located under the
“Device” pull-down menu.
8.
Place the transducer block into “Out of Service (O/S)” mode. Set the
filter time constant to the desired value (perform for all transducer
blocks).
9.
Select the “Load into PG/PG” option (UPLOAD), located under the
“Device” pull-down menu.
10. Place the Transducer block into Auto mode.
AI blocks
1.
Place the AI block into “Out of Service (O/S)” mode and
then UPLOAD.
2.
Configure the channel for each block by right-clicking on the
parameter for each block. Select “On-line Option” and then the
channel. Choose a option and UPLOAD.
3.
Right-click on the “Process Scale Variable” parameter. Indicate the
desired upper, lower and unit values. Download these parameters
onto the device (performed for each block). UPLOAD.
4.
Right-click on the “Output Signal” parameter. Indicate the desired
upper, lower and unit values. Download these parameters onto the
device (performed for each block).
5.
Select the “Load into PG/PG” option (UPLOAD), located under the
“Device” pull-down menu.
6.
To set User Warning and Alarm Limits, right-click on “Upper Limit
Alarm,” “Upper lImit Warning,” “Lower Limit Warning,” and “Lower
Limit Alarm.” Select values and UPLOAD.
7.
Place the AI block into Auto mode.
Summary of Contents for 3244MV
Page 2: ......
Page 4: ......
Page 46: ...Reference Manual 00809 0100 4799 Rev BA September 2002 Model 3244MV A 12 ...
Page 58: ...Reference Manual 00809 0100 4799 Rev BA September 2002 Model 3244MV B 12 ...
Page 60: ...Reference Manual 00809 0100 4799 Rev BA September 2002 Model 3244MV Index 2 ...
Page 61: ......