Monitoring Phase
The monitoring phase starts once the learning process is complete. The
algorithm compares the current values to the baseline values of the mean and
standard deviation. During this phase the algorithm computes the percent
change in mean and standard deviation to determine if the defined limits are
violated.
SPM Configuration
SPM_Bypass_Verification
“Yes” means that the verification of the baseline is turned off while “No”
indicates the learned baseline is compared to the next current calculated
value to ensure a good baseline value. The recommended value is NO.
SPM_Monitoring_Cycle
SPM_Monitoring_Cycle is the length of time the process values are taken and
used in each calculation. A longer monitoring cycle may provide a more stable
mean value with the default set at 15 minutes.
SPM#_Block_Tag
Enter the Block Tag of the function block containing the parameter to be
monitored. Block tag must be entered, since there is no pull-down menu to
select the tag. The tag must be a valid “Block Tag” in the device. The default
block tags from the factory are:
AI 1400
AI 1500
PID 1600
ISEL 1700
CHAR 1800
ARITH 1900
SPM can also monitor “out” parameters from other devices. Link the “out”
parameter to an input parameter of a function block residing in the device, and
set up SPM to monitor the input parameter.
SPM#_Block Type
Enter the Block Type of the function block containing the parameter to be
monitored.
SPM#_Parameter Index
Enter the Parameter Index of the parameter to be monitored.