![Rosemount 3144P User Manual Download Page 143](http://html1.mh-extra.com/html/rosemount/3144p/3144p_user-manual_1487451143.webp)
Reference Manual
00809-0100-4021, Rev FB
August 2011
B-9
Rosemount 3144P
ROSEMOUNT 3144P WITH F
OUNDATION
FIELDBUS
Approved Manufacturing
Locations
Rosemount Inc. – Chanhassen, Minnesota, USA
Rosemount Temperature GmbH – Germany
Emerson Process Management Asia Pacific – Singapore
European Union
Directive Information
The most recent revision of the European Union Declaration of Conformity
can be found at www.emersonprocess.com.
ATEX Directive (94/9/EC)
Rosemount Inc. complies with the ATEX Directive.
Electro Magnetic Compatibility (EMC) (2004/108/EC)
EN 61326-1: 2006, EN 61326-2-3: 2006
Hazardous Locations
Installations
North American Certifications
Factory Mutual (FM) Approvals
I5
FM Intrinsically Safe / FISCO and Non-incendive
Certificate Number: 3012752
Intrinsically Safe / FISCO for use in Class I, II, III, Division 1, Groups A,
B, C, D, E, F, and G;
Temperature code: T4 (T
amb
= – 60 °C to 60 °C)
Zone marking: Class I, Zone 0, AEx ia IIC T4 (T
amb
= – 50 °C to 60 °C)
Intrinsically safe and Non-incendive when installed in accordance with
Rosemount drawing 003144-5075.
Non-incendive for use in Class, Division 2, Groups A, B, C, and D.
Suitable for use in Class II/III, Division 2, Groups F and G.
Non-incendive when installed in accordance with Rosemount drawing
03144-5075.
Temperature Codes: T6 (T
amb
= – 60 °C to 50 °C);
T5 (T
amb
= – 60 °C to 75 °C)
E5 Explosion-proof for Class I, Division 1, Groups A, B, C, and D.
Dust Ignition-proof for use in Class II/III, Division 1, Groups E, F, and G.
Certificate Number: 3012752
Explosion-proof and Dust Ignition-proof when installed in accordance
with Rosemount drawing 03144-0320. Indoor and outdoor use. Type 4X.
Temperature code: T5 (T
amb
= – 50 to 85 °C)
NOTE
For Group A, seal all conduits within 18 inches of enclosure; otherwise,
conduit seal not required for compliance with NEC 501-15(A)(1).
Non-incendive for use in Class I, Division 2, Groups A, B, C, and D.
Suitable for use in Class II/III, Division 2, Groups F and G.
Non-incendive when installed in accordance with Rosemount drawing
03144-5075.
Temperature Codes: T5 (T
amb
= – 60 °C to 75 °C);
T6 (T
amb
= – 60 °C to 50 °C)