Reference Manual
00809-0100-4021, Rev FB
August 2011
A-9
Rosemount 3144P
Local Display
Displays all DS_65 measurements in the Transducer and Function Blocks
including Sensor 1, Sensor 2, differential and terminal (body) temperatures.
The display alternates up to four selected items and can display up to five
digits in engineering units (°F, °C, °R, K,
, and millivolts). Display settings are
configured at the factory according to the transmitter configuration (standard
or custom), and these settings can be reconfigured in the field using a Field
Communicator or DeltaV. In addition, the LCD can display DS_65 parameters
from other devices. Besides the configuration of the meter, sensor diagnostic
data is displayed. If the measurement status is Good, the measured value is
shown. If the measurement status is uncertain, “uncertain” is shown in
addition to the measured value. If the measurement status is Bad, the reason
for the bad measurement is shown.
NOTE
When ordering a spare electronics module assembly, the LCD transducer
block will display the default parameter.
Turn-on Time
Specification performance is achieved less than 20 seconds after power is
applied to the transmitter when the damping value is set to 0 seconds.
Status
If self-diagnostics detect a sensor burnout or a transmitter failure, the status of
the measurement will be updated accordingly. The status may also send the
PID output to a safe value.
F
OUNDATION
Fieldbus Parameters
Backup Link Active Scheduler (LAS)
The transmitter is classified as a device link master, meaning it can function
as a Link Active Scheduler (LAS) if the current link master device fails or is
removed from the segment. The host or other configuration tool downloads
the schedule for the application to the link master device. In the absence of a
primary link master, the transmitter will claim the LAS and provide permanent
control for the H1 segment.
Function Blocks
Resource Block
• Contains physical transmitter information including available memory,
manufacture identification, device type, software tag, and unique
identification
• PlantWeb Alerts enable the full power of the PW digital architecture by
diagnosing instrumentation issues, communicating the details, and
recommending a solution
Schedule Entries
25 (max.)
Links
30 (max.)
Virtual Communications Relationships (VCR)
20 (max.)