Reference Manual
300550EN, Rev AA
December 2010
6-19
Rosemount 2240S
Section 6. Service and Troubleshooting
6.3.4
Measurement
Status for the
WLS
Table 6-7 shows measurement status for a water level sensor connected to a
2240S Multi-input Temperature Transmitter.
You can view status registers by using the
View Diagnostic Registers
function
or the
View Input Registers
function in TankMaster WinSetup, see
“Diagnostics” on page 6-4 and “Viewing Input and Holding Registers” on
page 6-2.
Table 6-7. Measurement status
for water level sensor
Message
Description
Status
Input register no. 500
(1)
.
Bit 0: No Device Connected
Bit 1: Device reports value under or above 15%
Bit 2: Saturated Low
Bit 3: Saturated High
Bit 4: Relative Pressure
Bit 7: Saturated
Bit 8: In Calibration Mode
Bit 11: Frozen Value
Bit 12: Option Not Available
Bit 13: Power Up
Bit 14: SW_HW_Error
Bit 15: Invalid
(1) The register number refers to the internal Input Register in the 2240S database.
Primary Variable (PV)
Input register no. 502.
Primary value from the connected sensor
Unit
Input register no. 504.
Measurement unit such as Feet, Meters, Inches etc.
Summary of Contents for 2240S
Page 2: ......
Page 4: ......
Page 84: ...Reference Manual 300550EN Rev AA December 2010 Rosemount 2240S A 6 Appendix A Reference Data ...
Page 99: ......