6
Verify configuration
Verify the configuration using any HART capable configuration tool or Local
Operator Interface (LOI) - option code M4. Configuration instructions for a
Field Communicator and LOI are included in this step.
6.1 Verifying configuration with a Field Communicator
A Rosemount 2051 DD must be installed on the Field Communicator to verify
configuration. Fast Key sequences for the latest DD are shown in
Table 6-1
.
For Fast Key sequences using legacy DD's, contact your local Emerson
™
representative.
Note
Emerson recommends installing the latest DD to access the complete
functionality. Visit
Emerson.com/Field-Communicator
for information on
updating the DD Library.
Procedure
1. Verify device configuration using the Fast Key sequences in
Table 6-1
.
2. A check (
✓
) indicates the basic configuration parameters. At
minimum, these parameters should be verified as part of configuration
and startup.
Example
Table 6-1: Device Revision 9 and 10 (HART7), DD Revision 1 Fast Key
Sequence
Function
Fast Key Sequence
HART 7
HART 5
✓
Alarm and Saturation
Levels
2, 2, 2, 5, 7
2, 2, 2, 5, 7
✓
Damping
2, 2, 1, 1, 5
2, 2, 1, 1, 5
✓
Range Values
2, 2, 2
2, 2, 2
✓
Tag
2, 2, 7, 1, 1
2, 2, 7, 1, 1
✓
Transfer Function
2, 2, 1, 1, 6
2, 2, 1, 1, 6
✓
Units
2, 2, 1, 1, 4
2, 2, 1, 1, 4
Burst Mode
2, 2, 5, 3
2, 2, 5, 3
Custom Display
Configuration
2, 2, 4
2, 2, 4
Date
2, 2, 7, 1, 4
2, 2, 7, 1, 3
February 2019
Quick Start Guide
Quick Start Guide
19