The covers must only be capable of being released or removed with
the aid of a tool to comply with applicable ordinary locations
requirements.
Example
Figure 5-2: Wiring
Aluminum
Polished 316 SST
DP
A
B
D
E
C
DP
A
B
D
E
C
A. Minimize distance
B. Trim shield and insulate
C. Protective grounding terminal
D. Insulate shield
E. Connect shield back to the power supply ground
5.1 Grounding for transient terminal block
Ground termination is provided on the outside of the electronics housing and
inside the terminal compartment. These grounds are used when the transient
protection terminal blocks are installed. It is recommended that 18 AWG or
larger wire is used to connect housing ground to earth ground (internal or
external).
If the transmitter is currently not wired for power up and communication,
follow
Connect the wiring and power up
step
Step 1
through
Step 8
. When
the transmitter is properly wired, refer to
Figure 5-2
for internal and external
transient grounding locations.
Note
The Rosemount 2051HT polished 316 SST housing only provides ground
termination inside the terminal compartment.
Quick Start Guide
February 2019
18
Rosemount 2051 Pressure Transmitter Quick Start Guide