Technical data
Page 70
RES-5011
Version 2
Line voltage
Connected between neutral conductor and one line conductor:
110 VAC -15%…300 VAC +10%
or
Connected between two line conductors:
110 VAC -15%…415 VAC +10%
The voltage between the line conductor and ground must not be more
than 300 VAC.
Power supply system
Balanced TN or TT system, max. 415 VAC
Installation category III
Operation in potential-free systems (e.g. an IT system) is only per-
mitted after consultation with ROPEX.
Line frequency
47…63 Hz, automatic adjustment to frequencies in this range
Current consumption
(primary current of
impulse
transformer)
I
max
= 5 A (duty cycle = 100%)
I
max
= 25 A (duty cycle = 20%, cycle duration 1 min)
24 VDC supply
voltage
Terminals 5+7
24 VDC, Imax = 200 mA
Tolerance: ±10%
SELV or PELV supplied from max. 300 VAC, Cat II
Measuring range
Secondary voltage U
R
:
0.4…120 VAC
Secondary current I
R
:
30…500 A (with PEX-W4/-W5 current transformer)
ROPEX Application Report
EtherNet/IP
TM
inter-
face
2 Ethernet switch ports RJ45
Wiring: IEC 61784-5-3
Data transfer rate: 10 or 100 Mbit/s
Data transport layer: Ethernet II, IEEE 802.3
Addressing: DHCP or selectable with rotary coding switch
ACD and DLR support: Yes
Heatsealing band
type and temperature
range
The temperature range and temperature coefficient settings can also be specified
in the ROPEX visualization software (
section 8.12 "USB interface for visualiza-
" on page 61) in addition to using the rotary coding
switch or via the EtherNet/IP
TM
interface (see below):
Temperature range:
200 °C, 300 °C, 400 °C, or 500 °C
Temperature coefficient: 400…4000 ppm/K (variable setting range)
Five different ranges can be set using the rotary coding switch or via the EtherNet/
IP
TM
interface:
Temperature coefficient 1100 ppm/K, 0…300 °C (e.g. Alloy 20)
Temperature coefficient 780 ppm/K, 0…300 °C (e.g. Alloy L)
Temperature coefficient 1100 ppm/K, 0…500 °C (e.g. Alloy A20)
Temperature coefficient 780 ppm/K, 0…500 °C (e.g. Alloy L)
Temperature coefficient 3500 ppm/K, 0…300 °C (e.g. NOREX)
Please take the necessary setting from the ROPEX application report
!
!