11.6.1 Controller status
The controller status is sent on request and contains all important information about the status of the
RESISTRON
®
Temperature Controller RES-5009. In the event of an alarm, an exact error diagnosis can be per-
formed on the basis of the error message (
section 9.15 "Error messages" on page 49).
The controller status is coded as follows:
Bit no.
Name
Meaning
0…1
Setpoint no.
Number of the last setpoint used (0…3)
2
Control active
0: Measurement mode
1: Control mode
3
Temperature OK
0: Actual value is outside the specified temperature monitoring band
1: Actual value is inside the specified temperature monitoring band
4
Alarm
0: no alarm
1: Alarm active
5
AUTOCAL blocked
0: “AUTOCAL” function possible
1: “AUTOCAL” function not possible (cooling off phase)
6
AUTOCAL active
0: “AUTOCAL” function is not executed
1: “AUTOCAL” function is being executed
7
Hold active
0: Hold is not active
1: Hold is active
8…11
Error message
Error no. 0…13 (
section 9.15 "Error messages" on page 49)
12
START requested
START request was received
13
Start input
0: Start from external start input “START with setpoint 0” or
Start request via CAN
1: Start from external start input “START with setpoint 1”
14
Undervoltage
0: Supply voltage in working range
1: Supply voltage too low (undervoltage)
15
Temperature
reached
When the actual temperature has reached 95% of the setpoint temperature,
this status bit is set. As soon as the control mode is ended or an alarm occurs,
this status bit will be reset.