11.5.1 Temperature setting (setpoint setting)
Up to four different setpoints can be permanently stored in the RESISTRON
®
Temperature Controller RES-5009.
The stored setpoints are retained even after a power interruption. The setpoints can be read back on request. By
programming the setpoints accordingly, it is possible, for example, to switch between pre-heat and main heat, or
a certain setpoint can be reached slowly in different stages (“ramp”). The maximum settable setpoint T
max
is deter-
mined by the selected temperature range (see CAN message address 0008 and CAN message address 0004,
value 12). Here, temperature ranges of 200 °C, 300 °C, 400 °C and 500 °C can be defined.
Setpoints greater than T
max
will be limited to T
max
with subsequent storage. If “variable” is selected at alloy/range
(CAN message address 0008) (value 11), T
max
is determined by the selected temperature range (CAN message
address 13
h
) and by the value stored at “maximum setpoint” (CAN message 000B).
The setpoint specification for the welding temperature must be greater than 40 °C. If it is smaller, no heat-up pro-
cess will take place when the start/stop command is activated.
001F
-1, 0…40
Save calibration temperature channel 6 (in °C); -1
variable
0020
-1, 0…40
Save calibration temperature channel 7 (in °C); -1
variable
0021
400…4000
variable temperature coefficient (TCR in ppm/K), channel 1
(valid if the value 11
d
was sent under address 0008)
0022
400…4000
variable temperature coefficient (TCR in ppm/K), channel 2
(valid if the value 11
d
was sent under address 0008)
0023
400…4000
variable temperature coefficient (TCR in ppm/K), channel 3
(valid if the value 11
d
was sent under address 0008)
0024
400…4000
variable temperature coefficient (TCR in ppm/K), channel 4
(valid if the value 11
d
was sent under address 0008)
0025
400…4000
variable temperature coefficient (TCR in ppm/K), channel 5
(valid if the value 11
d
was sent under address 0008)
0026
400…4000
variable temperature coefficient (TCR in ppm/K), channel 6
(valid if the value 11
d
was sent under address 0008)
0027
400…4000
variable temperature coefficient (TCR in ppm/K), channel 7
(valid if the value 11
d
was sent under address 0008)
0050
0...255
Measurement pause with specified duration
Ending the measurement pause when measurement pause duration = 0
(
section 9.2.4 "Measurement pause (MP)" on page 32)
0051
0...7
Channel selection
(
section 9.2.5 "Channel selection (CH0…CH2)" on page 33)
F002
any
Factory setting of all parameters (
section 12 "Factory settings" on page 89)
Address
(hex)
Value
(dec.)
Meaning