Device functions
Version 1
RES-5009
Page 41
this takes longer than the parameterised time, error no. 304 is output and the alarm output switches on
(
section 9.15 "Error messages" on page 49).
The Heat-up time monitoring function must be enabled for use in the parameter data (standard setting: Heat-up
time monitoring off).
Further information
• CANopen:
section 10.7.2 "Parameter data" on page 63 (CANopenobject 400F
h
)
• ROPEX CAN:
section 11.5 "Receiving CAN messages" on page 77 (address 0011
h
)
CAUTION
The heat-up time monitoring function is only available for the start signal transmitted via CAN and
the 24 VDC signal START 0. There is no heat-up time monitoring for the 24 VDC signal START 1
9.4.9
Hold mode
The behaviour for the output of the ACTUAL temperature via the CANopen/CAN protocol can be parameterised
via the parameter data as follows:
1.
“Off” (factory setting)
The current ACTUAL temperature is always output in real time.
2.
“On”
The same ACTUAL temperature that was current at the end of the last welding phase is output. After the con-
troller is switched on, the real ACTUAL temperature is displayed until the end of the first heating phase.
3.
“2 Sec.”
At the end of a welding phase, the current ACTUAL temperature is output for a further 2 seconds via the CAN-
open/CAN protocol. Afterwards, the ACTUAL temperature is output again in real time until the end of the next
welding phase.
The Hold mode only affects output of the ACTUAL temperature over the CANopen/CAN protocol and the numeric
temperature display in the ROPEX visualisation software.
Output of the ACTUAL temperature over the analogue output of the controller or the graphic drawing in the ROPEX
visualisation software is not changed by this.
Setpoint
95% of set-
ACTUAL temperature
Time
Heat-up time
Alarm
304
Moni-
toring