Controller functions
Version 1
RES-430
Page 45
10.6
Temperature setting (set point selection)
The heatsealing temperature can be set by means of menu step 101.
The maximum value of the setting range is limited either by the maximum value specified with
step 206 in the Configuration menu or by the temperature range set with step 205.
The set point that is selected for the heatsealing temperature must be greater than 40°C. If not, the heatsealing
band will not be heated up when the "START" signal is activated or the "HAND" key (assuming step 213 has not
been locked in the Configuration menu and the display is in the home position) is pressed.
The set heatsealing temperature is displayed in the main menu once it has been entered.
10.7
Temperature indication / actual value output
If the display is in the home position, the ACTUAL temperature is indicated there as a digital value and as a
dynamic bar.
The heating and control process can thus be monitored at any time.
In addition, the RES-430 outputs an analog 0…10VDC signal, which is proportional to the real ACTUAL temper-
ature, at terminals 10+11.
Voltage values:
0VDC
0°C
10VDC
300°C or 500°C
(depending on the controller configuration)
!
RES-430
10
max. 5mA
11
0V
R=33ohms
Actual value
output
0…10VDC
-
+
0…10VDC
Temperature
meter
e.g. ATR-3