Dimensions
Page 14
RES-409
Version 1
7
Dimensions
8
Montage und Installation
See also section 1 "General information" on page 3.
Installation and startup may only be performed by technically trained, skilled persons who are
familiar with the associated risks and warranty provisions.
8.1
Installation procedure
Proceed as follows to install the RES-409 RESISTRON
®
temperature controller:
1. Switch off the line voltage and verify that all circuits are deenergized.
2. The supply voltage specified on the nameplate of the RESISTRON
®
temperature controller must be identical
to the line voltage that is present in the plant or machine. The line frequency is automatically detected by the
temperature controller in the range from 47Hz to 63Hz.
3. Install the RESISTRON
®
temperature controller on a standard top hat rail (DIN TS35 rail according to
DIN EN 50022) in the electrical cabinet. If several controllers are installed on one top hat rail, the minimum
clearance specified in section 6 "Technical data" on page 11 must be allowed between them.
75.0
90.0
113.
0
1
35.
0
!