Modifications (MODs)
Page 46
RES-407
Version 1
MOD 46 (as of April 2005)
Additional terminal for "Temperature OK" signal. If this modification is installed, the RES-407 checks whether the
ACTUAL temperature is within a settable tolerance band ("OK" window) on either side of the SET temperature.
The lower (
) and upper (
) tolerance band limits are configured in the factory to -10K and +10K.
These values can be set independently of one another in the ROPEX visualization software (
gnostic interface/visualization software (as of April 2005)" on page 33).
If the actual temperature is inside the specified tolerance band when the "START" signal is activated, the output
signal is activated as well (see graph below):
If the actual temperature leaves the tolerance band, the output signal is deactivated again. The output signal then
remains deactivated, even if the actual temperature subsequently returns to the tolerance band.
It is thus possible to check - as part of the monitoring concept, for instance - whether the output signal is still active
at the end of the heatsealing process, in other words whether the actual temperature has remained within the
defined tolerance band throughout the entire process.
The output signal is not deactivated again until the next "START" signal is activated or until an alarm is signaled.
MOD 46 ("Temperature OK" signal) cannot be used in combination with MOD 40 ("Temperature
reached" signal).
Δϑ
lower
Δϑ
upper
Set
Signal
Set+
Δϑ
lower
Set+
Δϑ
upper
Actual value
Time
Time
Not conduct.
Conductive
„Temp. OK“
!