Technical data
Version 1
RES-407
Page 43
Reference voltage
+10VDC / ±5%, I
max
= 5mA
Digital logic levels
Terminals 5, 6, 7
LOW (0V): 0…2VDC, electrically isolated
HIGH (24VDC): 12…30VDC (max. current input 6mA)
Reverse polarity-protected
Switching output for
"Temp. reached"
signal
(MOD 40)
and
„Temp. OK” signal
(MOD 46)
U
max
= 30VDC
I
max
= 50mA
U
ON
< 2V (saturation voltage)
Alarm output
U
ON
< 3V (saturation voltage), electrically isolated,
short-circuit proof
Up to March 2005:
I
max
= 40mA
As of April 2005:
I
max
= 200mA
As of April 2005, the output can also be inverted by means of a plug-in jumper.
Maximum load
(primary current of
impulse transformer)
I
max
= 5A (duty cycle = 100%)
I
max
= 25A (duty cycle = 20%)
Power dissipation
max. 20W
Ambient
temperature
+5…+45°C
Degree of protection
IP20
Installation
If several controllers are installed on one top hat rail
(DIN TS35 rail), a clearance of at least 20mm should
be allowed between them.
The moving clip required for fastening must be facing
down for mounting on a horizontal top hat rail.
End holders to mechanical fix the controller must be fitted at both ends for moun-
ting on a vertical top hat rail.
Weight
Approx. 0.7kg (incl. connector plug-in parts)
Housing material
Plastic, polycarbonate, UL-94-V0
Connecting cables
Type / cross-sections
Rigid or flexible; 0.2…2.5mm² (AWG 24…12)
Plug-in connectors
If ferrules are used, they must be crimped in accordance
with DIN 46228 and IEC/EN 60947-1.
This is essential for proper electrical contact in the terminals.
!