Device functions
Seite 40
UPT-6010
Version 2
If any new events occur while this page is displayed, you do not see them until you refresh the list by clicking on
the "Protocol" menu again.
8.8.5
Graphic page
The temperature controller has an internal memory which can store temperature curves over a period of up to
5 seconds. This memory is automatically filled when the ST bit is set. You can display or export the memory con-
tents on the Graphic page.
By clicking on "Refresh", you cause the graphic data to be downloaded from the memory of the temperature con-
troller and displayed again.
"Clear" clears all data from the memory (disconnecting the 24 VDC supply voltage has the same effect).
The vertical lines mark the beginning of a new heatsealing impulse (ST bit set). A negative set point indicates the
start of a new impulse in the exported data. Cooling processes are not normally visible because they take place
when the ST bit is reset.
8.8.6
Calibration page
This page is first available as from firmware version 303.
The temperature controller stores the absolute calibration resistance of each channel (Calibration resistance ch.
0…7) with an resolution of 0.1 mΩ.
The calculation of the respective calibration resistance is done at the end of the AUTOCAL function
(
section 8.5.1 "Automatic zero calibration AUTOCAL (AC)" on page 24).
The initial calibration resistances (Initial calibration resistance ch. 0…7) are calculated if the Master-AUTOCAL
function is executed (
section 8.5.5 "Master AUTOCAL (MA)" on page 26).
!