Page 62
19
Link settings between the DI-DO are changed
†
Event Type consists of a combination of bits. If the hexadecimal value is 0x3101, it indicates Bit.[15:12] = 3
(Trip), Bit.[11:8] = 1 (Phase A), Bit.[7:0] = 01 (Inverse OCR).
In other words, the type of the
event is “A phase trip by Inverse OCR”.
‡
From the product version 3.0, DI8 to DI10 have been deleted.
T4 : Interlock Function Setup
Value
Descriptions
0x0000
N (Disable)
0x0001
Y (Enable)
T5 : Motor Operation Status
Value
Descriptions
0x0000
By CB Status
0x0001
By Current Value
T6 - T8 : Reserved
T9 : Relay Function
Value
Descriptions
0x0000
Disable
0x0001
Trip
0x0002
Alarm
0x0003
T & A (Trip & Alarm)
0x0004
Test
0x0005
FA(free alarm)
†
†
Applicable
only for ‘Definite time SGR2
from the product version 3
T10 : Aux. Relay Setup
Value
Descriptions
0x0000
None
0x0001
DOUT 1
0x0002
DOUT 2
0x0003
DOUT 3
0x0004
DOUT 4
0x0005
DOUT 5
0x0006
DOUT 6
0x0007
DOUT 7
0x0008
DOUT 8
0x0009
DOUT 9
0x000A
DOUT 10