Page 53
MOTOR Protection Section
Address
Attribute
Value
Format
Descriptions
THR[49]
43341
R/W
Function
UINT 16
Refer to “Value Table T9”
43342
R/W
0.50
–
15.00 / 0.01 A
S2 UINT16
Rated Motor Current [Im]
43343
R/W
1.00
–
1.50 / 0.01
S2 UINT16
Constant k
43344
R/W
1
–
600 / 1 min
UINT 16
Heat Rise Time Constant
τ
43345
R/W
0.00
–
1.00 / 0.01 x Im
S2 UNIT 16
Previous Load Current [Ip]
43346
R/W
Reserved
UINT 16
Reserved
43347
R/W
1
–
6000 / 1 sec
UINT 16
Cooling TC (Running)
43348
R/W
1
–
6000 / 1 sec
UINT 16
Cooling TC (Stopped)
•••
Invalid
UINT16
•••
43350
Invalid
UINT16
Stall/Lock[51LR]
43351
R/W
Function
UINT 16
Refer to “Value Table T9”
43352
R/W
0.50
–
10.00 / 0.01A
S2 UINT16
Rated Motor Current [Im]
43353
R/W
1.00
–
20.00 / 0.01 x Im
S2 UNIT16
Pickup Value
43354
R/W
0.05
–
60.00 / 0.01 sec
S2 UINT16
Time Delay
Starting Overcurrent
43355
R/W
Function
UINT 16
Refer to “Value Table T9”
43356
R/W
0.50
–
10.00 / 0.01 A
S2 UINT16
Rated Motor Current [Im]
43357
R/W
1.00
–
20.00 / 0.01 x Im
S2 UNIT16
Permissible Start Current [Is]
43358
R/W
0.1
–
600.0 / 0.1 sec
S1 UNIT16
Permissible Start Time
43359
R/W
0.10
–
0.80 / 0.01 x Is
S2 UNIT16
Start Pickup Current
43360
R/W
N/Y
UNIT16
Refer to “Value Table T4”
51LR Interlock
43361
R/W
N/Y
UNIT16
Refer to “Value Table T4”
OCGR Interlock
UCR
43362
R/W
Function
UINT 16
Refer to “Value Table T9”
43363
R/W
0.10
–
5.00 / 0.01 A
S2 UINT16
Pickup value
43364
R/W
0.1
–
600.0 / 0.1 sec
S1 UINT16
Delay
43365
R/W
CB/Current
UINT 16
Refer to “Value Table T5”
Motor Status
•••
Invalid
UINT16
•••
43370
R/W
Save Request for MOTOR Relay
(Save Address :
43341 - 43365)
UINT16
0x00FF = Save Request
0x0000 = Do Not Save