Page 51
NSOVR section
Address
Attribute
Measurement
Format
Descriptions
Definite time NSOVR
43291
R/W
Function
UINT16
Refer to “Value Table T9”
43292
R/W
Tap (Pickup value)
UINT16
5 - 110 / 1V
43293
R/W
Delay
S2 UINT16 0.05 - 60.00 / 0.01 sec
43294
R/W
Phase Rotation
UNIT16
0 : ABC
1 : ACB
43295
R/W
NSOVR Save Request
(Save Address : 43291 - 43294)
UINT16
0x00FF = Save Request
0x0000 = Do Not Save
•••
Invalid
UINT16
•••
43300
Invalid
UINT16
OVGR section
Address
Attribute
Measurement
Format
Descriptions
Definite time OVGR
43301
R/W
Function
UINT16
Refer to “Value Table T9”
43302
R/W
Tap (Pickup value)
UINT16
10 - 110 / 1 V
43303
R/W
Delay
S2 UINT16 0.05 - 60.00 / 0.01 sec
Instantaneous OVGR
43304
R/W
Function
UINT16
Refer to “Value Table T9”
43305
R/W
Tap (Pickup value)
UINT16
10 - 110 / 1 V
43306
R/W
OVGR Save Request
(Save Address : 43301 - 43305)
UINT16
0x00FF = Save Request
0x0000 = Do Not Save
•••
Invalid
UINT16
•••
43320
Invalid
UINT16