Page 49
OCGR section
Address
Attribute
Measurement
Format
Descriptions
Inverse OCGR
43221
R/W
Function
UINT16
Refer to
“Value Table T9”
43222
R/W
Selected Curve
UINT16
Refer to “Value Table T13”
43223
R/W
Tap (Pickup value)
S2 UINT16 0.10 - 2.50 / 0.01 A
43224
R/W
Level (Multiplier)
S2 UINT16 0.05 - 1.20 / 0.01
Definite time OCGR
43225
R/W
Function
UINT16
Refer to
“Value Table T9”
43226
R/W
Tap (Pickup value)
S2 UINT16 0.10 - 2.50 / 0.01 A
43227
R/W
Delay
S2 UINT16 0.05 - 60.00 / 0.01 sec
Instantaneous OCGR
43228
R/W
Function
UINT16
Refer to “Value Table T9”
43229
R/W
Tap (Pickup value)
S1 UINT16 0.1 - 50.0 / 0.1 A
43230
R/W
OCGR Save Request
(Save Address : 43221 - 43234)
UINT16
0x00FF = Save Request
0x0000 = Do Not Save
Inverse OCGR2
43231
R/W
Function
UINT16
Refer to “Value Table T9”
43232
R/W
Selected Curve
UINT16
Refer to “Value Table T13”
43233
R/W
Tap (Pickup value)
S2 UINT16 0.10 - 2.50 / 0.01 A
43234
R/W
Level (Multiplier)
S2 UINT16 0.05 - 1.20 / 0.01
•••
Invalid
UINT16
•••
43240
Invalid
UINT16
OVR section
Address
Attribute
Measurement
Format
Descriptions
Definite time OVR
43241
R/W
Function
UINT16
Refer to “Value Table T9”
43242
R/W
Tap (Pickup value)
UINT16
60 - 270 / 1 V
43243
R/W
Delay
S2 UINT16 0.05 - 60.00 / 0.01 sec
Instantaneous OVR
43244
R/W
Function
UINT16
Refer to “Value Table T9”
43245
R/W
Tap (Pickup value)
UINT16
60 - 270 / 1 V
43246
R/W
OVR Save Request
(Save Address : 43241 - 43245)
UINT16
0x00FF = Save Request
0x0000 = Do Not Save
•••
Invalid
UINT16
•••
43260
Invalid
UINT16
Summary of Contents for ACCURA 7500