Page 36
Protection Part
DIO Status and Control section
Address
Attribute
Measurement
Format
Descriptions
Digital Input / Output Status and On/Off Control
41201
R
Digital Input channel 1
UINT16
0x00FF = On
0x0000 = Off
41202
R
Digital Input channel 2
UINT16
0x00FF = On
0x0000 = Off
41203
R
Digital Input channel 3
UINT16
0x00FF = On
0x0000 = Off
41204
R
Digital Input channel 4
UINT16
0x00FF = On
0x0000 = Off
41205
R
Digital Input channel 5
UINT16
0x00FF = On
0x0000 = Off
41206
R
Digital Input channel 6
UINT16
0x00FF = On
0x0000 = Off
41207
R
Digital Input channel 7
UINT16
0x00FF = On
0x0000 = Off
41208
R
Digital Input channel 8
†
UINT16
0x00FF = On
0x0000 = Off
41209
R
Digital Input channel 9
†
UINT16
0x00FF = On
0x0000 = Off
41210
R
Digital Input channel 10
†
UINT16
0x00FF = On
0x0000 = Off
41211
R/W
Digital Output channel 1
UINT16
0x00FF = On
0x0000 = Off
41212
R/W
Digital Output channel 2
UINT16
0x00FF = On
0x0000 = Off
41213
R/W
Digital Output channel 3
UINT16
0x00FF = On
0x0000 = Off
41214
R/W
Digital Output channel 4
UINT16
0x00FF = On
0x0000 = Off
41215
R/W
Digital Output channel 5
UINT16
0x00FF = On
0x0000 = Off
41216
R/W
Digital Output channel 6
UINT16
0x00FF = On
0x0000 = Off
41217
R/W
Digital Output channel 7
UINT16
0x00FF = On
0x0000 = Off
41218
R/W
Digital Output channel 8
UINT16
0x00FF = On
0x0000 = Off
41219
R/W
Digital Output channel 9
UINT16
0x00FF = On
0x0000 = Off
41220
R/W
Digital Output channel 10
UINT16
0x00FF = On
0x0000 = Off
CB Status Input and On/Off Control, Alarm output control
41221
R
CB Status Input
UINT16
0x00FF = On (Close)
0x0000 = Off (Open)
41222
R/W
CB Close Command
UINT16
0x00FF = Close
0x0000 = None
41223
R/W
CB Open Command
UINT16
0x00FF = Open
Summary of Contents for ACCURA 7500