Accura 2350-TEMPS User Guide
Chapter 2 Accura 2350-TEMPS Operation/Setup
ⓒ
2020 Rootech Inc. All Rights Reserved
Page 13
Operation Mode
Accura 2350-TEMPS module performs the following functions with the SET
button.
Mode
Description
Display mode
Displays the module ID and the internal and external temperatures of the panel
where it is installed
Event mode
If an event occurs, the screen automatically changes to the event mode.
While an event occurs, the maximum temperature blinks on the screen.
The event LED also blinks, and its color changes from green to red. Users can change
the event mode to the display mode by long pressing the SET button.
Setup mode
Configures the module ID, temperature unit, events and remote control
settings
Functions
Internal/External Temperature Measurement
Item
Description
Location of temperature
measurement
Channel 1
Internal temperature measurement of the panel
Channel 2
External temperature measurement of the panel
Measuring range
-20 to 100
℃
Measurement accuracy
2% FS
1
@ -20 to 100
℃
Temperature event
Internal temperature
Detects the occurrence of an
“
Over
”
temperature
event
2
based on the threshold value for the
internal temperature event
External temperature
Detects the occurrence of an "Over" temperature
event
2
based on the threshold value for the
external temperature event
Difference
between
internal/external temperatures
(internal temperature - external
temperature
Detects the occurrence of an "Over" temperature
event
2
based on the threshold value for the
difference
between
internal/external
temperatures
1. Full Scale(FS) indicates 100
°
C.
2. A
n “
Over" temperature event indicates the event that occurs when the measured value rises above the threshold
value for event detection.
3. A
n “Over” event consist
s of a start event and an end event.
Temperature Event
Users can perform separate setup for different types of events mentioned above.
A
n
“
Over" temperature
event occurs when the measured temperature rises above the threshold value for event detection.
A
n
“Over” event consists of a start event and an end event.
Summary of Contents for ACCURA 2350-TEMPS
Page 1: ......