Chapter 4 Accura 2300 Operation/Setup
Accura 2300/2350 User Guide
Page 140
ⓒ
2011 Rootech Inc. All Rights Reserved
Measurement Setup
Voltage Connection
Setup range
Description
3P4U [default]
3-Phase 4-wire [3P4W]
3P3U
3-Phase 3-wire [3P3W]
1P3U
Single-phase 3-wire [1P3W]
1P2U
Single-phase 2-wire [1P2W]
3P3O
1
3-Phase 3-wire Open-Delta [3P3O]
1. “3P3O” is setup menu for some older Accura 2300 that is not supported for 3P3W voltage connection in Accura 2300 for
3-phase 3-wire voltage connection. It works as 3P3W connection even if it is set to 3P3O connection.
PT Rating
Ratio of primary and secondary line-to-line voltage ratio is used as conversion ratio for primary voltage.
Regardless of voltage connection for measurement, always PT primary and secondary line-to-line voltage
should be input.
Setup range
Description
Pr[d][d][d][d][d][d]
1
PT primary line-to-line voltage rating
000001 – 999999
1 - 999999
[default 380]
Sc[d][d][d]
1
PT secondary line-to-line voltage rating
001 – 999
1 - 999
[default 380]
1. d
decimal
Primary and secondary line-to-line voltage for each connection method is as follows. In case of direct
connection without using PT, primary and secondary line-to-line voltage should be input as the same value.
Fig 4.18 3-phase 4-wire connection[3P4W]: PT Primary V
AB
, Secondary V
12