PRTxxMF series readers Operating Manual.doc
2019-01-29
17/54
5.5.
D
OOR
B
ELL
F
UNCTION
By default the
[F1]: Door Bell
and
[F2]: Light Bulb
keys operate as door bell buttons. When
pressed they produce continues sound generated by the internal buzzer and optionally can trigger
the
[47]: Door Bell
output (if programmed). Both indications last for 5 seconds and cease
automatically even when the key is still pressed. The door bell indication can be trigged either from
primary or secondary reader. Also, the door bell can be triggered through the separate press of [#]
key. This method is especially useful when F1 and F2 keys were programmed to other control
function or don’t exist on the particular device.
Note: When [#] key is pressed to conclude PIN then door bell indication is not generated. Only
separate, individual press of [#] key triggers door bell signalling.
5.6.
F
UNCTION
K
EYS
As mentioned above, by default, in standalone mode (both
Full
or
Simple Standalone Mode
)
pressing the F1 or F2 key results in door bell signalling however this rule is not valid if you program
any output with one of following functions:
[48]
,
[49]
,
[50]
or
[51]
.
If you program any output with function
[48]: AUX1 Momentary
or
[50]: AUX1 Toggle
then
pressing of the F1 key will no longer trigger door bell but it will trigger AUX1 output.
If you program any output with function
[49]: AUX2 Momentary
or
[51]: AUX2 Toggle
then
pressing of the F2 key will no longer trigger door bell it will trigger AUX2 output.
Note: If you press function key on primary or secondary reader the system will react in the same
way.
5.7.
D
OOR
A
LARM
The
Door Alarm
is a compound state which consists of one or more situations which are related to
controlled door:
Forced Entry
Prealarm
Door Ajar
The
Door Alarm
state can be signaled over the dedicated output
[46]: Door Alarm
and
optionally on the internal buzzer (option:
Door Alarm indication on internal buzzer
). For
indication of each particular type of alarm reader uses different signal modulation.
Door Alarm
Event
Priority
Output modulation method
Alarm situation
Forced
Entry
High
Sequence:
Active - 4 s, Pause - 4 s
A door was opened in
unauthorized method. This
state can be cleared by
entering any valid identifier or
it disappears automatically
after 3 minutes.
Prealarm
Medium
Sequence:
Active - 1 s, Pause - 1 s
Detection of five consecutive
usage of unknown card/PIN
made within 5 minutes.
Entering valid card/PIN clears
fault attempt counter. During
Prealarm
state
reader
disables reading of cards and
PIN-s thus blocking the users’
identification for 5 minutes.
Door Ajar
Low
Sequence:
Active - 1 s, Pause - 1 s, Active - 1 s,
Door not closed within
Door
Open Timeout
. This state
can be cleared by entering
Summary of Contents for PRT MF Series
Page 47: ...PRTxxMF series readers Operating Manual doc 2019 01 29 47 54 ...
Page 48: ...PRTxxMF series readers Operating Manual doc 2019 01 29 48 54 ...
Page 49: ...PRTxxMF series readers Operating Manual doc 2019 01 29 49 54 ...
Page 50: ...PRTxxMF series readers Operating Manual doc 2019 01 29 50 54 ...
Page 51: ...PRTxxMF series readers Operating Manual doc 2019 01 29 51 54 ...
Page 52: ...PRTxxMF series readers Operating Manual doc 2019 01 29 52 54 ...
Page 53: ...PRTxxMF series readers Operating Manual doc 2019 01 29 53 54 ...