PR402DR-SET Installation Manual   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2020-10-07 

 

1/2 

 

Roger Access Control System 

PR402DR-SET Installation Manual 

Controller firmware version: 1.18.6 or newer 

Product version: 2.0 

Document version: Rev. B 

 

This  document  contains  minimum  information  that  is  necessary  for  initial  setup 
and  installation  of  the  kit.  The  detailed  description  of  configuration  parameters 
and  functionalities  of  all  components  is  specified  in  respective  Operating 
manuals available a

www.roger.pl

I

NTRODUCTION

 

PR402DR-SET  is  designed  to  control  single  door  in  RACS  4  system.  The  door 
can  be  read-in  or  read-in/out  type  when  equipped  with  PRT  series  readers 
(RACS  CLK/DTA),  Wiegand  interface  readers  or  Magstripe  interface  readers. 
The  kit  includes  PR402DR-BRD  access  controller  and  ME-1  metal  box  with 
18VAC/40VA  transformer.  The  box  is  adapted  to  installation  of  7Ah  battery  for 
emergency  supply.  All  elements  of  controlled  door  including  readers  and  door 
lock can be supplied from the kit. 

P

RELIMINARY CONFIGURATION

 

Preliminary  configuration  requires  addressing  of  the  controller  on  RS485  bus  in 
range  of  00-99.  All  controllers  on  this  bus  must  have  unique  addresses.  It  is 
recommended to configure the address of controller by means of jumpers. Other 
methods are explained in controller’s manual. 
 

 

Fig. 1 Addressing with jumpers 

C

ONFIGURATION WITH 

PR

 

M

ASTER PROGRAM

 

Configuration  with  PR  Master  enables  to  define  the  logic  of  controller  including 
users  and  access  rights.  More  information  is  given  in  PR  Master  manual.  The 
communication 

with 

controller 

requires 

connection 

to 

computer 

via 

communication  interface  (e.g.  UT-4DR,  UT-2USB,  RUD-1)  or  via  CPR32-NET-
BRD network controller. 

M

EMORY RESET

 

Memory  reset  procedure  resets  all  settings  to  default  ones.  RS485  address 
which is configured with jumpers remains unchanged. 

Memory reset procedure: 

1.  Disconnect power supply from controller. 
2.  Short CLK and IN1 lines. 
3.  Restore power supply - LED OPN (green) will start to pulsate. 
4.  Disconnect CLK and IN1. 
5.  After  a  few  seconds  the  controller  will  restart  automatically  and  switch  to 

normal mode. 

F

IRMWARE UPDATE

 

New  firmware  can  be  uploaded  to  the  controller  with  RogerISP  software.  The 
latest firmware file is available a

www.roger.pl

Firmware update procedure: 

1.  Connect  the  device  to  RUD-1  interface  (fig.  2)  and  connect  the  RUD-1  to 

computer’s USB port. 

2.  Place jumper on FD contacts (fig. 1). 
3.  Restart  the  device  (switch  power  supply  off  and  on  or  press  RST  button) 

LED SYS (orange) indicator will be switched on. 

4.  Start  RogerISP  software,  select  serial  port  with  RUD-1  interface  port,  select 

the option 

USB-RS485 Converter

 and indicate path to firmware file (*.hex). 

5.  Click 

Update

 to start firmware upload with progress bar displayed. 

6.  When the  update is finished,  remove jumper from FDM contacts  and restart 

the device. 

 

Fig. 2 Connection of the controller to RUD-1 interface for firmware update 

Note: 
1. If the controller is not responding after firmware update and LED SYS (orange) 
indicator is switched on then it is necessary to start memory reset procedure. 
2. If firmware update is not successful for any reason then repeat the procedure. 
3.  UT-2USB  interface  can  be  used  instead  of  RUD-1  interface  for  firmware 
update. 

P

OWER SUPPLY

 

The kit is supplied from 18VAC/40VA transformer. The metal box offers space for 
installation of typical  7Ah backup battery  which is connected to BAT+ and BAT- 
terminals of PR402DR-BRD controller. 
 

 

Fig. 3 PR402DR-SET 

 

The installation can be done only by qualified person with all 
necessary certificates concerning connection and maintenance 
of 230VAC and low voltage networks. 

 

Prior to starting the installation it is necessary to ensure that 
230 VAC circuit is disconnected. All works inside the box must 
be carried out with 230VAC supply voltage disconnected. 

 

It is forbidden to use the kit without properly executed and 
operational earthing system. 

T

AMPER DETECTOR

 

The metal box is  equipped  with  door  contact  which  can be connected to  one of 
the  inputs  (e.g.  IN8)  and  GND  terminal  of  the  controller.  The  anti-sabotage 
function can be assigned to the input with PR Master software. 