Start Up
Applying Power to the Drive
❏
4.
Apply AC power and control voltages to the drive.
If any of the six digital inputs are configured to “Stop – CF”
(CF = Clear Fault) or “Enable,” verify that signals are present or
reconfigure [Digital Inx Sel]. If an I/O option is not installed (i.e. no I/O
terminal block), verify that [Digital Inx Sel] is not configured to “Stop –
CF” or “Enable.” If this is not done, the drive will not start. Refer to
& Alarm Descriptions on page 3-3
for a list of potential digital input
conflicts. If a fault code appears, refer to
❏
5.
Proceed to Start-Up Routines.
Status Indicators
Figure 1.1 Drive Status Indicators
#
Name
Color
State
Description
➊
PWR (Power)
Green
Steady Illuminates when power is applied to the drive.
➋
PORT
Green
–
Status of DPI port internal communications (if present).
MOD
Yellow
–
Status of communications module (when installed).
NET A
Red
–
Status of network (if connected).
NET B
Red
–
Status of secondary network (if connected).
➊
➋
Frame 9 shown