204
Rockwell Automation Publication 1783-UM007F-EN-P - September 2016
Chapter 7
Configure Switch Features
Configure Time Synchronization via the Logix Designer Application
To configure time synchronization, follow these steps.
1. In the navigation pane, click Time Sync Configuration.
2. From the Clock Type pull-down menu, choose a mode.
The available modes vary based on the switch model.
3. To complete the remaining fields, refer to the figure and table that
corresponds to your mode.
Sync Interval
Type the time interval, specified as the logarithmic mean in seconds, for sending synchronization messages.
Valid values:
• -1—half second
• 0—1 second
• 1— 2 seconds
Default: 0 (1 second)
Sync Fault Limit
Type the maximum clock offset before PTP attempts to reacquire synchronization.
Valid values: 50…500000000 nanoseconds
Default: 50000 nanoseconds
IMPORTANT:
We recommend against setting the sync limit below the default (50000 nanoseconds). Use values below 50000 nanoseconds only in
networks with a very high-precision grandmaster clock. These networks have a critical need to keep very sensitive devices synchronized.
Vlan Id
To configure PTP on a VLAN of a trunk port, type the VLAN ID. Only PTP packets in the VLAN you specify are processed. PTP packets from other
VLANs are dropped. You can only enable PTP on one VLAN on a trunk port.
Valid values: 1…4094
The default is the native VLAN of the trunk port.
Table 36 - NTP-PTP Clock Mode Fields (Continued)
Field
Description
Mode
Page
Boundary
End to End
Forward
NTP-PTP Clock
Summary of Contents for ArmorStratix 5700 series
Page 12: ...12 Rockwell Automation Publication 1783 UM007F EN P September 2016 Table of Contents Notes...
Page 14: ...14 Rockwell Automation Publication 1783 UM007F EN P September 2016 Preface Notes...
Page 16: ...16 Rockwell Automation Publication 1783 UM007F EN P September 2016 Summary of Changes Notes...
Page 486: ...486 Rockwell Automation Publication 1783 UM007F EN P September 2016 Appendix A DataTypes Notes...
Page 547: ......