Installation Guidelines

Follow these guidelines to make sure that your VersaView® 6300B box PC or VersaView 6300T box thin client provides service with excellent reliability.

When choosing the installation site, consider the following:
- The site must have sufficient power
- The site must be indoors and non-hazardous
- The site must not expose the computer to direct sunlight

The box PC or box thin client can operate in a surrounding air temperature range as follows:
- 0…55 °C (32…131 °F) with the Intel Atom x5 processor
- 0…50 °C (32…122 °F) with the Intel Atom x7 processor
- 0…50 °C (32…122 °F) with the Intel Core i3, Core i5, and Core i7 processors
The surrounding air temperature must not exceed the maximum temperature for your box PC or box thin client, especially when either one is mounted in an enclosure.

The box PC or box thin client can be stored in a surrounding air temperature range of -10…+60 °C (14…140 °F).

The humidity of the surrounding air must not exceed 80% noncondensing.

Mounting Requirements

Follow these requirements to mount the VersaView 6300B box PCs or VersaView 6300T box thin clients.

Choose a suitable mounting height.

Only mount the box PC or box thin client in a vertical (upright) position, where the ground screw is at the bottom, as shown i

Figure 1 on page 3

.

Mount the box PC or box thin client so there is at least 20 mm (0.8 in.) of clearance on each side for the circulation necessary for cooling.

Required Tools and Hardware for Installation

The following tools are needed for the mounting bracket installations.

A drill and 4 mm drill bit 

#2 Phillips screwdriver

Four M4x20 stainless steel screws (customer supplied)

Safety  glasses

Install a Box PC or Box Thin Client With the Book Mount Bracket

Install the box PC or box thin client in an industrial or control room environment, which uses some form of power isolation from the public, low voltage mains.

1.

Use the dimensions in 

Figure 1 on page 3

 to locate and drill holes for the four M4x20 stainless steel screws.

2.

Install the four customer-supplied screws but leave enough space to hang the brackets. 

3.

Align the keyhole slots on the top bracket with the top two screws.

4.

Align the slots on the bottom bracket with the bottom two screws.

5.

Slide the computer downward until all four screws are at the top of each bracket slot.

6.

Tighten the four screws.

Install a Box PC With the DIN Rail Bracket

Install the box PC in an industrial or control room environment, which uses some form of power isolation from the public, low voltage mains.

1.

Refer to the 6300B-DRF

x

 Box PC dimensions in 

Figure 1 on page 3

.

2.

Install the box PC on a DIN rail.

ATTENTION: 

For DIN rail mounting applications, only safety glasses are needed.

IMPORTANT

A DIN rail is not supplied with the bracket. An installed DIN rail is the responsibility of the customer.

Summary of Contents for Allen-Bradley VersaView 6300B

Page 1: ...ing to the Connect Peripherals section The picture for 6300B BMFx and 6300B DRFx models The digital input output I O item to the picture and table The USB cable length stipulation 4 Changed the heading from Connect DC Power to Connect DC Power Wiring 4 Added the subheading For 6300B BMAx and 6300B BMBx Box PCs and 6300T BAx1 Box Thin Clients to the Install the DC Connector Assembly section 5 Added...

Page 2: ... at the bottom as shown in Figure 1 on page 3 Mount the box PC or box thin client so there is at least 20 mm 0 8 in of clearance on each side for the circulation necessary for cooling Required Tools and Hardware for Installation The following tools are needed for the mounting bracket installations A drill and 4 mm drill bit 2 Phillips screwdriver Four M4x20 stainless steel screws customer supplied...

Page 3: ...0 75 230 9 06 19 0 75 6 0 24 4 x Ø 4 1 8 25 0 98 25 0 98 100 3 97 150 5 9 5 5 0 22 100 3 97 150 5 9 256 5 10 1 268 10 6 Front View Vertical Upright Position Side View 6300B BMAx Box PCs and 6300T BAx1 Box Thin Clients 6300B BMBx Box PCs 221 8 7 6300B BMFx Box PCs 47 1 85 4 5 0 18 127 25 5 01 140 5 51 20 0 79 100 3 94 8 25 0 32 77 3 03 100 3 94 20 0 79 4 x Ø 4 5 0 18 Front View Vertical Upright Pos...

Page 4: ...wer Wiring Follow these steps to connect the box PC or box thin client to a DC power source Install the Ground Wire 1 Turn off the main power switch or breaker 2 Remove the supplied nut eyelet terminal and washers from the ground screw 3 For earth ground fasten a 2 5 mm2 14 AWG or larger external wire to the eyelet terminal Use a ground wire with an insulation color that is approved by local inspe...

Page 5: ...es 9 Use cutting pliers to cut the excess part of the cable tie D 10 Install the white label supplied with the kit E 11 Align and install the other connector clamp half to complete the assembly F 12 Reconnect the DC terminal block with the connector assembly to the computer chassis Torque the DC terminal block flange screws to the values in Figure 2 13 Proceed to Connect DC Power on page 6 IMPORTA...

Page 6: ...ally starts the computer after it is plugged into a power source For VersaView 6300B box PCs with a Microsoft Windows operating system OS you must read and accept an End User Setup procedure Do not disconnect power from the system until after the Windows Setup procedure is completed If power is disconnected during this procedure it can result in a corrupted system image Table 1 LEDs and Buttons on...

Page 7: ...ate and time 5 Watchdog LED Green The watchdog is working Red The watchdog timer has expired 6 PLC status LED 2 7 BUS status LED 2 8 Power on reset button Turns the computer on or off 9 System reset button Forces an internal reset as if power was lost temporarily and then returned IMPORTANT Use this button only if there are no better options like keyboard or mouse commands System reset can cause d...

Page 8: ...on its website at rok auto pec Your comments help us serve your documentation needs better If you have any suggestions on how to improve our content complete the form at rok auto docfeedback For technical support visit rok auto support Rockwell Otomasyon Ticaret A Ş Kar Plaza İş Merkezi E Blok Kat 6 34752 İçerenkÖy İstanbul Tel 90 216 5698400 EEE YÖnetmeliğine Uygundur This computer contains a sea...