PowerFlex Digital DC Drive User Manual -
Publication 20P-UM001C-EN-P - July 2008
Troubleshooting
4-7
Table 4.B Fault Cross Reference by Number
Clearing Alarms
Alarms are automatically cleared when the condition that caused the alarm
is no longer present.
Alarm Descriptions
The status of the alarms can be viewed in
[Drive Alarm 1].
Table 4.C Alarm Descriptions and Actions
No.
(1)
(1)
Fault numbers not listed are reserved for future use.
Fault
No.
(1)
Fault
Auxiliary Input
Drive Overload
Power Failure
Sustained Curr
AC Undervoltage
Port 1 Adaptor
Arm Overvoltage
Port 2 Adaptor
Fld Current Loss
Port 3 Adaptor
Heatsink OvrTemp
Port 4 Adaptor
Main Contactor
Port 5 Adaptor
13
Over Current
Port 1 DPI Loss
Motor Over Temp
Port 2 DPI Loss
Overspeed
Port 3 DPI Loss
Inverting Fault
Port 4 DPI Loss
STune Overspeed
Port 5 DPI Loss
STune Stalled
Encoder Loss
STune LoadHi
EEPROM Error
STune CurLimit
Hardware Fault
STune FrictionLo
Interrupt Error
STune Timeout
Dsp Error
STune Aborted
Alarm
Type Description
AnalogCflct
➁
More than one of the drive's reference inputs (Pars
and
[Anlg Inx
[Encoder Out Sel]) are set
to "Speed Ref A" or "Speed Ref B". This alarm takes precedence over the
“EncoderCflct” alarm when both are present. Refer to
Reference Selection on page D-5
for a graphical representation of the drive's
reference selections.
Arm
Overvoltage
➀
There is a possible overvoltage on the armature circuit or Par
[Rated
Motor Volt] is set too low for the application. Refer to the “Arm Overvoltage”
fault description on
for more information.
Auxiliary Input
➀
An auxiliary input interlock is open or a voltage (+15 - 30 V) or reference
signal is missing for the digital input set to 14 “Aux Fault”. Refer to the
“Auxiliary Input” fault description on
for more information.
BipolarCflct
➁
[Direction Mode] is set to “Bipolar” or “Reverse Dis” and one or more
of the following digital input functions is configured: “Fwd/Reverse,” “Run
Forward,” “Run Reverse,” “Jog Forward” or “Jog Reverse.”