Programming and Parameters
3-65
PowerFlex Digital DC Drive User Manual -
Publication 20P-UM001C-EN-P - July 2008
IN
PUT / OUTPUT
Digita
l Inputs
133
134
135
136
137
138
139
140
141
142
143
144
[Digital In1 Sel]
[Digital In2 Sel]
[Digital In3 Sel]
[Digital In4 Sel]
[Digital In5 Sel]
[Digital In6 Sel]
[Digital In7 Sel]
[Digital In8 Sel]
[Digital In9 Sel]*
[Digital In10 Sel]*
[Digital In11 Sel]*
[Digital In12 Sel]*
Selects the function driven by the digital input.
Refer to
Option Definitions for [Digital Inx Sel] on page 3-66
*These parameters are used to configure the digital inputs on
the I/O Expansion circuit board.
Note: Option 35 was changed from “Fld Weaken En” to “Force
MinFld” and option 64 “Invert Flt” was added with firmware
version 2.001.
Options:
Default:
Default:
Default:
Default:
Default:
Default:
Default:
Default:
Default:
Default:
Default:
Default:
2 =
3 =
11 =
1 =
17 =
18 =
19 =
31 =
0 =
0 =
0 =
0 =
“Stop/CF”
“Start”
“Jog”
“Enable”
(1)
“Speed Sel 1”
“Speed Sel 2”
“Speed Sel 3”
“Contactor”
“Not Used”
“Not Used”
“Not Used”
“Not Used”
1
A digital input (1-8 only) must be configured for “Enable”.
2
This option is not available (“Reserved”) for digital inputs 9 - 12.
File
Gr
oup
No.
Parameter Name & Description
See
page 3-2
for symbol descriptions
Values
Related
0 =
“Not Used”
17 = “Speed Sel 1”
34 = “Field Reg En”
51 = “Diam Reset”
1 =
“Enable”
(1) (2)
18 = “Speed Sel 2”
35 = “Force MinFld”
52 = “DiamCalc Dis”
2 =
“Stop/CF”
(2)
19 = “Speed Sel 3”
36 = “Freeze Ramp”
53 = “Torq Wind En”
3 =
“Start”
(2)
20 = “PI Enable”
37 = “UsrDefinedA0”
54 = “Speed Match”
4 =
“Fwd/Reverse”
(2)
21 = “PI Hold”
38 = “UsrDefinedA1”
55 = “Diam I/D En”
5 =
“Run”
(2)
22 = “PI Reset”
39 = “UsrDefinedA2”
56 = “Wind/Unwind”
6 =
“Run Forward”
(2)
23 = “PI Invert”
40 = “UsrDefinedA3”
57 = “Diam Preset0”
7 =
“Run Reverse”
(2)
24 = “Local”
41 = “UsrDefinedA4”
58 = “Diam Preset1”
8 =
“Run Level”
(2)
25 = “Acc2 & Dec2”
42 = “UsrDefinedA5”
59 = “Taper Enable”
9 =
“RunFwd Level”
(2)
26 = “Accel 2”
43 = “UsrDefinedA6”
60 = “Spd DemandEn”
10 = “RunRev Level”
(2)
27 = “Decel 2”
44 = “UsrDefinedA7”
61 = “Winder Side”
11 = “Jog”
(2)
28 = “MOP Inc”
45 = “Droop Enable”
62 = “PI-PD Enable”
12 = “Jog Forward”
(2)
29 = “MOP Dec”
46 = “PD Enable”
63 = “Jog TW En”
13 = “Jog Reverse”
(2)
30 = “Fast Stop”
47 = “PID SetptSel”
64 = “Invert Flt”
14 = “Aux Fault”
31 = “Contactor”
48 = “PI Cent vs0”
15 = “Clear Faults”
32 = “MOP Reset”
49 = “PI Cent vs1”
16 = “Auto/Manual”
33 = “TorqueReduce”
50 = “Diam Calc”