Option Module Parameters
B-3
PowerFlex 750-Series Drive DeviceNet Option Module User Manual
Publication 750COM-UM002A-EN-P
09 [Net Rate Cfg]
Sets the network data rate at which the Option
Module communicates if the Data Rate switch
(see
) is set to position
“3.” (Updates Device Parameter 10 - [Net
Rate Act] after a reset.)
Default:
0 = 125kbps
Values:
0 = 125kbps
1 = 250kbps
2 = 500kbps
3 = Autobaud
Type:
Read/Write
Reset Required: Yes
10 [Net Rate Act]
Displays the actual network data rate being
used by the Option Module.
Default:
0 = 125kbps
Values:
0 = 125kbps
1 = 250kbps
2 = 500kbps
3 = Autobauding
Type:
Read Only
11 [COS Status Mask]
Sets the mask for the 32-bit Logic Status word.
Unless they are masked out, the bits in the
Logic Status word are checked for changes
when the Option Module is allocated using
COS (Change of State). If a bit changes, it is
reported as a change in the Change of State
operation.
If the mask bit is “0” (Off), the bit is ignored. If
the mask bit is “1” (On), the bit is checked.
Important: The bit definitions in the Logic
Status word for PowerFlex 750-Series drives
are shown in
.
Default:
0000 0000 0000 0000
0000 0000 0000 0000
Minimum:
0000 0000 0000 0000
0000 0000 0000 0000
Maximum:
1111 1111 1111 1111
1111 1111 1111 1111
Type:
Read/Write
Reset Required: No
12 [COS Fdbk Change]
Sets the amount of acceptable error (positive
or negative) that the Feedback word can
change before it is reported as a change in the
COS (Change of State) operation.
Default:
0
Minimum:
0.000
Maximum:
3.40282 x 10
38
Type:
Read/Write
Reset Required: No
13 [COS/Cyc Interval]
Displays the amount of time that a scanner will
wait to check for data in the Option Module.
When COS (Change of State) data exchange
has been configured, this is the maximum
amount of time between scans. Scans will
occur sooner if data changes.
When Cyclic data exchange has been
configured, this interval is the fixed time
between scans.
Default:
0.000 seconds
Minimum:
0.000 seconds
Maximum:
65.535 seconds
Type:
Read Only
14 [Reset Module]
No action if set to “0” (Ready). Resets the Option
Module if set to “1” (Reset Module). Restores
the Option Module to its factory default settings if
set to “2” (Set Defaults). This parameter is a
command. It will be reset to “0” (Ready) after the
command has been performed.
When performing a Set Defaults, the drive
may detect a conflict. If this occurs, the drive
will not allow a Set Defaults action. You must
resolve the conflict before attempting a Set
Defaults action for the Option Module.
Default:
0 = Ready
Values:
0 = Ready
1 = Reset Module
2 = Set Defaults
Type:
Read/Write
Reset Required: No
Parameter
No. Name and Description
Details
!
ATTENTION: Risk of injury or equipment damage exists. If the Option
Module is transmitting I/O that controls the drive, the drive may fault when
you reset the Option Module. Determine how your drive will respond before
resetting the Option Module.